Energy Recovery Ventilation
The product helps save energy and drive down operation costs of heaters and coolers by recycling thermal energy
(energy load) efficiently.
Interlocked operation with DVM
Controls of interlocked operation for energy saving, One remote controller can be used with air conditioners.
Mounted for DX-coil unit for outdoor air treatment
This improves the dry and cooling effect in the summer and humidifying effect in the winter.
Humidity Control
Fresh air conditions are guaranteed by recovering moisture in winter while exhausting it in summer.
The high efficiency Humidifier element can be mounted.(Optional product)
Low Noise and Low Power
With highly efficient motor and optimized system design, operation noise and electric consumption is minimized.
The high efficiency filter
This protects the heat exchange element and cleans the polluted outdoor air before it enters the indoor room.
Operation at Cold Area
Optimized automatic ventilation operation is conducted to prevent condensation and air volume reduction.
How to use this unit
This unit should be used with air conditioners. Air conditioning is impossible only by this unit, because this unit does not
have temperature control function. (It’s capacity is too small in order to control the room temperature to the whole)
And should be operated in combination with standard indoor units. (Interlocked operation) Independent operation is
possible, however, temperature setting by remote controller is impossible. In this ON/OFF operation by thermostat depends
on factory setting, however, this value is changeable by installation/service mode on site. Model selection should be done
not by cooling capacity but by ventilating air flow rate.
Refer to following capacities when using the product with outdoor unit: RHF050KHEA - 3.6kW, RHF100KHEA - 7.1 kW
Clean-UP operation
Prevent the odor and dust of other places such as bathroom and kitchen from entering inside by making supply air greater
than the exhaustion air. (You can reverse this procedure to make the exhaustion air bigger than the supply air.)
Features of your new product
RHF050KHEA_IB,IM_E_32885-3.indd 2
2011-10-12 오후 5:30:06