Setting the Option Switch and Function of the Keys (Continued)
Dip Switch Setup
K13 K14K15 K16
K9 K10K11 K12
K5 K6 K7 K8
����
����
����
Switch No.
Function (Cooling capacity compensation)
K7
K8
ON
ON
No Cooling Frequency compensation (Default)
ON
OFF
Frequency compensation 105% (frequency*compensation value)
OFF
ON
Frequency compensation 110% (frequency*compensation value)
OFF
OFF
Frequency compensation 115% (frequency*compensation value)
Switch No.
Function (Communication Tracking)
K5
ON
Set indoor unit address manually
OFF
Set indoor unit address automatically
Switch No.
Function (Night silence)
K9
K10
ON
ON
Not use Night silence (Default)
ON
OFF
Night silence Step_1 (Basic Fan RPM in EEPROM)
OFF
ON
Night silence Step_2 (10% speed reduction of Step_1)
OFF
OFF
Night silence Step_3 (20% speed reduction of Step_1)
Switch No.
Function (Heating capacity compensation)
K11
K12
ON
ON
No high pressure target (Default)
ON
OFF
High pressure target [standard 0.2MPa (2.03 kgf/cm²)]
OFF
ON
High pressure target [standard -0.1 MPa (1.01 kgf/cm²)]
OFF
OFF
High pressure target [st0.1 MPa (1.01 kgf/cm²)]
Switch No.
Function (All electric current Option)
6kW 7kW 8kW 11kW 14kW 16kW
K13
K14
ON
ON
All electric current (Default)
12.5A 14.8A 16.6A
24A
26A
28A
ON
OFF
All electric current I_Down_OP1
10.5A 12.5A
14A
23A
24A
26A
OFF
ON
All electric current I_Down_OP2
9A
11A
12A
20A
22A
24A
OFF
OFF
All electric current I_Down_OP3
9A
10A
10A
20A
20A
20A
Standard:3.0MPa