Locating the Units (Continued)
Outdoor unit base mount and anchor bolt position
(Unit : mm)
660
878
147
163
174
When tightening the anchor bolt
Tighten the rubber washer to prevent the outdoor unit bolt connection
part from corroding.
Rubber washer
Installing the drain pipe
When installing 1 outdoor unit
Outdoor unit
(Rear side)
More than
1/50 gradient
Open to air
Drain
plug
Open the upside of connected parts of outdoor units to prevent inner pressure.
Do not install a trap in the drain pipe work and install with a 1/50 gradient or more.
Insulate the drain pipe and drain plug by using the insulation over 10mm.
Install a self-regulation heat cable to prevent the drain pipe from freezing.
When installing more than 1 outdoor unit
Outdoor unit
(Rear side)
More than 1/50 gradient
Open to air
Drain
plug
Outdoor unit
(Rear side)
Outdoor unit
(Rear side)
Drain pipe covered with
insulation
Caution When Installing Cover for Heating Air Direction Change
Parts shown in the picture is where the copper pipe may be passing by or the external plate
may be near the copper pipe. When using screw for installing the air direction changing device
such as heating air cover, check and make sure that it does not damage the copper pipe.
< Internal view from bottom>
Drain pipe
Insulation
(Unit : mm)
Anchor bolt position (ø7, 4 holes )
6/7/8kW
11/14/16kW
Anchor bolt position (ø7, 4 holes )