OH85N-D(K)/(LH85OHNDKGB/**)
Total open area of the ventilation holes and ratio
Follow the guide when combining the product with the enclosure unit.
–
If the instructions provided in this guide are not observed, the cooling system may not work properly and may cause
a malfunction, which will not be covered by warranty.
–
Calculating Total open area of the ventilation and Ventilation opening ratio
Total Area of the Ventilation: 181 x 89 = 16,109
mm
Total open area of Ventilation holes : 20 x 20 x 32 = 12,800
mm
181 mm
3 mm
20 mm
89 mm
Ventilation opening ratio:
Total open area of Ventilation holes
=
12,800
mm
x 100 = 79 %
Total Area of the Ventilation
16,109
mm
Precautions for enclosure unit designing
Consider the location of the IR Remote and Eco Sensor on your product when designing an enclosure unit.
–
The sensor may not work or cause the screen to darken if the sensor is sufficiently exposed.
IR Remote Sensor/ Eco Sensor
–
The guide for OH85N-D(K)/(LH85OHNDKGB/**) only applies when the product is used with an enclosure that has a
protective glass added to the front side.