ENGLISH-17
03
O
tHE
rS
Main
menu
Sub
menu
Function description
Setting value
Page
Save location
Value
Factory default
5
2
Indoor unit
discharge
temperature
setting/
checking 2)*
Use of discharge
temperature control
0 - No use, 1 - Use
0
01
Indoor unit
Cooling discharge temperature
8~18 °C
15
02
Indoor unit
Heating discharge temperature
30~43 °C
38
03
Indoor unit
3
Fresh duct
indoor unit
discharge
temperature
setting/
checking 2)*
Cooling discharge temperature
13~25 °C
18
01
Fresh duct
indoor unit
Heating discharge temperature
18~30 °C
25
02
Fresh duct
indoor unit
4
AHU Indoor
unit discharge
temperature
setting/
checking 2)*
Use of discharge
temperature control
0 - No use, 1 - Use
0
01
AHU Indoor unit
Cooling discharge temperature
8~25 °C
15
02
AHU Indoor unit
Heating discharge temperature
18~43 °C
38
03
AHU Indoor unit
7
1
View master
setting/
checking
Indoor unit view master setting/
checking
Indoor unit view
master address
(Example : 20 02 1F)
Indoor unit view
master
01~03
None
2
Mode master
indoor unit
setting/
checking
Mode master indoor unit
checking
Indoor unit master
address (Example :
20 02 1F)
none
01~03
None
3
Mode master indoor unit setting
6)*
0-No use, 1-Use,
2-Release 7)*
none
01
None
8
1
Status of automatic air volume setting
1
0
01
Indoor unit
2
Automatic air volume operation
1
0
01
Indoor unit
3
Automatic air volume voltage setting
1
2
01
Indoor unit
0
1
Reset
Factory setting
1
0
None
2
Power master reset 8)*
1
0
None
3
Outdoor units reset
1
0
None
1)* Relative temperature means that the wired remote controller only displays the temperature increase or decrease (± 3)
compared to the reference temperature . Reference temperature is determined by other controller's desired temperature
setting .
(Example : DMS set 24 °C (75 °F)
24 °C (75 °F) is reference temperature . Wired remote controller displays it as '0' )
2)* Only the celsius temperature unit is allowed when this function setting and checking in the service mode .
For the fahrenheit temperature, you need temperature conversion before this function setting and checking