VI
-25
I
NST
ALLA
TION
DVM PLUS
III
HR
Outdoor unit connection pipe size : (A1), (A2), (A3)
Branch joint : (D), (E), (F)
8HP
ø9.52
ø19.05
ø15.88
10HP
ø22.23
ø19.05
12HP
ø25.40
14HP
ø12.70
16HP
18HP
ø28.58
20HP
ø15.88
22HP
24HP
26~30HP
ø28.58
32~34HP
ø19.05
ø31.75
36~48HP
ø38.10
ø31.75
50~64HP
ø22.23
ø44.45
ø38.10
ø6.35
Pipe size (O.D. mm), (A)
Liquid
pipe
Gas
pipe
High
gas pipe
Outdoor
unit
Oil
balancing
pipe size
ø22.23
ø25.40
Model
Capacity of outdoor unit
MXJ-T3819K
Below 48 HP
MXJ-T4422K
Above 50 HP
MXJ-T3100K
Below 48 HP
MXJ-T3800K
Above 50 HP
■
Branch joint of outdoor unit’s multi connection (D)
Liquid &
Low gas pipe
High gas pipe
Total indoor unit’s capacity
Pipe size (O.D. mm)
Liquid Gas High
pipe
pipe
gas pipe
15.0 kW and below
ø15.88
ø15.88
Over 15.0~23.2 kW and below
ø9.52
ø19.05
Over 23.2~29.0 kW and below
ø22.23 ø19.05
Over 29.0~40.6 kW and below
ø12.70
ø25.40
ø22.23
Over 40.6~46.4 kW and below
ø28.58
Over 46.4~69.6 kW and below
ø15.88
ø25.40
Over 69.6~98.6 kW and below
ø19.05
ø31.75 ø28.58
Over 98.6~139.2 kW and below
ø38.10 ø31.75
Over 139.2 kW
ø22.23 ø44.45 ø38.10
Pipe size between branch joints : (B)
Select the pipe size according to the capacity sum of
indoor units which are air connected below this pipe.
Indoor unit’s
Pipe size (O.D. mm)
capacity
Liquid pipe
Gas pipe
2.2~5.6 kW
ø6.35
ø12.70
7.1~14.0 kW
ø9.52
ø15.88
Pipe size between branch joints and indoor unit (C)
Select the pipe size according to the indoor's capacity.
Model
Total indoor unit’ capacity
MXJ-YA1509K
15.0 kW and below
MXJ-YA2512K
Over 15.0 ~ 40.6 kW and below
MXJ-YA2812K
Over 40.6 ~ 46.4 kW and below
MXJ-YA2815K
Over 46.4 ~ 69.6 kW and below
MXJ-YA3119K
Over 69.6 ~ 98.6 kW and below
MXJ-YA3819K
Over 98.6 ~ 139.2 kW and below
MXJ-YA4422K
Over 139.2 kW
Liquid &
low
pressure
gas
Y-joint
(F)
■
Branch joint (
F
)
Model
Total indoor unit’ capacity
MXJ-YA1500K
23.2 kW and below
MXJ-YA2500K
Over 23.2 ~ 69.6 kW and below
MXJ-YA3100K
Over 69.6 ~ 139.2 kW and below
MXJ-YA3800K
Over 139.2 kW
High
pressure
gas
Y-joint
(F)
Outdoor unit
Model
8, 10, 12, 14 HP
MXJ-YA2512K
16 HP
MXJ-YA2812K
18, 20, 22, 24HP
MXJ-YA2815K
26, 28, 30, 32, 34HP
MXJ-YA3119K
36, 28, 40, 42, 44, 46, 48HP
MXJ-YA3819K
50HP~
MXJ-YA4422K
Liquid & Low
pressure gas
Y-joint
(E)
■
F
irst branch joint (E)
Select branch joint according to outdoor unit's capacity
Outdoor unit
Model
8 HP
MXJ-YA1500K
10 ~ 24 HP
MXJ-YA2500K
26 ~ 48 HP
MXJ-YA3100K
50HP ~
MXJ-YA3800K
High
pressure gas
Y-joint
(E)
(A)
(B)
A1 : Select the pipes according to the outdoor unit
capacity with following table.
A2 : Select the pipes according to sum of outdoor
unit capacities behind the outdoor joint with
following table.
A3 : Select the main pipe of outdoor units with the
following table.
12Hp
(A1)
(A1)
(A2)
(A1)
(F)
(D)
(A3)
(E)
(B)
(C)
14Hp
16Hp
*A1 : Pipes to the outdoor unit (Liquid, Gas, High pressure gas)
*A2 : Pipes between outdoor joint kits (Liquid, Gas, High pressure gas)
*A3 : Main pipes (Liquid, Gas, High pressure gas)
Pipe size(O. D.mm)
HP
Mark
Liquid
Low
High
gas
gas
12 HP (A1) ø12.70 ø25.40 ø22.23
14 HP (A1) ø12.70 ø25.40 ø22.23
16 HP (A1) ø12.70 ø28.58 ø22.23
26 HP (A2) ø19.05 ø31.75 ø28.58
42 HP (A3) ø19.05 ø38.10 ø31.75
❈
Example) 42HP of compact
combinations
06_Installation(02~45) 3/15/08 4:34 Page 25
Summary of Contents for Mini DVM
Page 4: ...DVM PLUS III I 4 1 products 01 41 3 14 08 22 01 Page 4 ...
Page 42: ...DVM PLUS III II 2 chapter2_Indoor units 002 051 3 14 08 22 09 Page 2 ...
Page 44: ...II 4 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 4 ...
Page 64: ...Indoor Units II 24 chapter2_Indoor units 002 051 3 14 08 22 09 Page 24 ...
Page 76: ...II 36 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 36 ...
Page 110: ...II 70 Indoor Units chapter2_Indoor units 052 107 3 14 08 22 15 Page 70 ...
Page 183: ...II 143 I NDOOR U NITS chapter2_Indoor units 108 143 3 14 08 22 38 Page 143 ...
Page 184: ...DVM PLUS III III 2 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 2 ...
Page 186: ...Outdoor Units III 4 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 4 ...
Page 504: ...DVM PLUS III IV 2 4 Accessories 02 31 3 6 08 13 59 Page 2 ...
Page 506: ...IV 4 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 4 ...
Page 516: ...IV 14 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 14 ...
Page 533: ...IV 31 A CCESSORIES 4 Accessories 02 31 3 6 08 13 59 Page 31 ...
Page 534: ...DVM PLUS III V 2 05 1_control systems 002 045 3 15 08 4 09 Page 2 ...
Page 536: ...Control Systems V 4 05 1_control systems 002 045 3 15 08 4 09 Page 4 ...
Page 614: ...Control Systems V 82 05 3_control systems 082 141 3 6 08 14 03 Page 82 ...
Page 674: ...Control Systems V 142 05 4 6_control systems 142 171 3 6 08 14 09 Page 142 ...
Page 696: ...V 164 Control Systems 05 4 6_control systems 142 171 3 6 08 14 09 Page 164 ...
Page 703: ...V 171 C ONTROL S YSTEMS 05 4 6_control systems 142 171 3 6 08 14 09 Page 171 ...
Page 704: ...DVM PLUS III VI 2 06_Installation 02 45 3 15 08 4 34 Page 2 ...
Page 706: ...VI 4 Installation 06_Installation 02 45 3 15 08 4 34 Page 4 ...