5-2. DVM design process example (Cooling)
(As for both cooling and heating units, it is necessary to review its design for heating)
1) Determine design conditions
Ô
Design temperature
2) Select preliminary indoor unit for each zone
Ô
Determine the type of indoor unit
Ô
Check cooling load per zone
Ô
Product power supply: 3-phase, 380V, 50Hz
Ô
Max. piping length (outdoor unit to the farthest indoor unit): 60m
Level difference: -20m (‘-’ means outdoor unit is installed at a location lower than indoor unit.)
Ô
Considering design temperature condition, select a larger indoor unit model than indoor load values at the
cooling capacity table by each indoor unit. (If latent heat load value is known, select an indoor unit that meets
both latent heat load and sensible heat load.)
❈
Design Temperature can differ from country to country or from region to
region.
Cooling
Outdoor
Indoor
33°C DB
19°C WB
Cooling
Outdoor
Indoor
33°C DB
19°C WB
Zone
A
B
C
D
E
F
G
Total cooling load (kW)
3.3
6.3
4.5
7.1
10.4
7.0
10.0
Sensible heat load of
cooling (kW)
2.2
5.0
3.0
4.9
8.0
5.1
7.0
Zone
A
B
C
D
E
F
G
Total cooling load (kW)
3.3
6.3
4.5
7.1
10.4
7.0
10.0
Sensible heat load of
cooling (kW)
2.2
5.0
3.0
4.9
8.0
5.1
7.0
Indoor unit type
Vivace
Slim duct
Mini 4way
4way
Slim duct
Ceiling
4way
Zone
A
B
C
D
E
F
G
Total cooling load (kW)
3.3
6.3
4.5
7.1
10.4
7.0
10.0
Sensible heat load of
cooling (kW)
2.2
5.0
3.0
4.9
8.0
5.1
7.0
Indoor unit type
Vivace
Slim duct
Mini 4way
4way
Slim duct
Ceiling
4way
Determined model
AVXWVH036 AVXDSH071 AVXCMH056 AVXC4H071 AVXDSH112 AVXTFH071 AVXC4H112
1. products(01~41) 3/14/08 22:01 Page 33
Summary of Contents for Mini DVM
Page 4: ...DVM PLUS III I 4 1 products 01 41 3 14 08 22 01 Page 4 ...
Page 42: ...DVM PLUS III II 2 chapter2_Indoor units 002 051 3 14 08 22 09 Page 2 ...
Page 44: ...II 4 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 4 ...
Page 64: ...Indoor Units II 24 chapter2_Indoor units 002 051 3 14 08 22 09 Page 24 ...
Page 76: ...II 36 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 36 ...
Page 110: ...II 70 Indoor Units chapter2_Indoor units 052 107 3 14 08 22 15 Page 70 ...
Page 183: ...II 143 I NDOOR U NITS chapter2_Indoor units 108 143 3 14 08 22 38 Page 143 ...
Page 184: ...DVM PLUS III III 2 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 2 ...
Page 186: ...Outdoor Units III 4 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 4 ...
Page 504: ...DVM PLUS III IV 2 4 Accessories 02 31 3 6 08 13 59 Page 2 ...
Page 506: ...IV 4 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 4 ...
Page 516: ...IV 14 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 14 ...
Page 533: ...IV 31 A CCESSORIES 4 Accessories 02 31 3 6 08 13 59 Page 31 ...
Page 534: ...DVM PLUS III V 2 05 1_control systems 002 045 3 15 08 4 09 Page 2 ...
Page 536: ...Control Systems V 4 05 1_control systems 002 045 3 15 08 4 09 Page 4 ...
Page 614: ...Control Systems V 82 05 3_control systems 082 141 3 6 08 14 03 Page 82 ...
Page 674: ...Control Systems V 142 05 4 6_control systems 142 171 3 6 08 14 09 Page 142 ...
Page 696: ...V 164 Control Systems 05 4 6_control systems 142 171 3 6 08 14 09 Page 164 ...
Page 703: ...V 171 C ONTROL S YSTEMS 05 4 6_control systems 142 171 3 6 08 14 09 Page 171 ...
Page 704: ...DVM PLUS III VI 2 06_Installation 02 45 3 15 08 4 34 Page 2 ...
Page 706: ...VI 4 Installation 06_Installation 02 45 3 15 08 4 34 Page 4 ...