I
-35
P
RODUCTS
3) Select preliminary outdoor units
Ô
Before selecting outdoor units, decide the permissible combination rates for indoor and outdoor unit.
➊
Determining permissible combination rates for indoor and outdoor units: Below 110%
❷
Calculate the sum of total capacity of the selected indoor units: 52.9kW (Refer to the table below)
52.9kW = [3.6kW + 7.1kW + 5.6kW + 7.1kW + 11.2kW + 7.1kW + 11.2kW]
❸
Select outdoor units
❹
Calculating actual combination rates of indoor and outdoor units
As outdoor unit RVXVHT180
✴✴
’s cooling capacity is 50.4kW,
Zone
A
B
C
D
E
F
G
Total cooling load (kW)
3.3
6.3
4.5
7.1
10.4
7.0
10.0
Sensible heat load of
cooling (kW)
2.2
5.0
3.0
4.9
8.0
5.1
7.0
Indoor unit type
Vivace
Slim duct
Mini 4way
4way
Slim duct
Ceiling
4way
Determined model
AVXWVH036 AVXDSH071 AVXCMH056 AVXC4H071 AVXDSH112 AVXTFH071 AVXC4H112
Indoor unit capacity (kW)
3.6
7.1
5.6
7.1
11.2
7.1
11.2
As the sum of all
indoor unit capacity
≤
Outdoor unit capacity
Permissible
combination rate,
All indoor unit capacity (52.9kW)
Actual combination rate is
=
Outdoor unit capacity (50.4kW)
approx. 105%.
As the sum of all
indoor unit capacity
≤
permissible combination rate
Outdoor unit
capacity.
OUTDOOR TYPE
Power Supply
Mode
Model
Performance
RVXVH(R)T160GE
3, 380~415, 50
HP/HR
16
44.8
152,900
50.4
172,000
RVXVH(R)T180GE
RVXVH(R)T200GE
3, 380~415, 50
HP/HR
20
56.0
191,000
63.0
215,000
RVXVH(R)T220GE
3, 380~415, 50
HP/HR
22
61.6
210,100
69.3
236,500
ø, V, Hz
-
HP
kW
Btu/h
✻
4
kW
Btu/h
-
Cooling
✻
1)
Heating
✻
2)
Horse Power
Capacity
Capacity Control Step
❈
Therefore, as 52.9kW/1.1 should meet outdoor unit capacity and less ( 52.9 kW/1.1
≤
outdoor unit capacity), cooling
capacity of outdoor unit should be larger than 48.1kW.
Hence, select the outdoor unit RVXVHT180GE(refer to the table below).
3, 380~415, 50
HP/HR
18
50.4
171,900
56.7
193,500
1. products(01~41) 3/14/08 22:01 Page 35
Summary of Contents for Mini DVM
Page 4: ...DVM PLUS III I 4 1 products 01 41 3 14 08 22 01 Page 4 ...
Page 42: ...DVM PLUS III II 2 chapter2_Indoor units 002 051 3 14 08 22 09 Page 2 ...
Page 44: ...II 4 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 4 ...
Page 64: ...Indoor Units II 24 chapter2_Indoor units 002 051 3 14 08 22 09 Page 24 ...
Page 76: ...II 36 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 36 ...
Page 110: ...II 70 Indoor Units chapter2_Indoor units 052 107 3 14 08 22 15 Page 70 ...
Page 183: ...II 143 I NDOOR U NITS chapter2_Indoor units 108 143 3 14 08 22 38 Page 143 ...
Page 184: ...DVM PLUS III III 2 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 2 ...
Page 186: ...Outdoor Units III 4 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 4 ...
Page 504: ...DVM PLUS III IV 2 4 Accessories 02 31 3 6 08 13 59 Page 2 ...
Page 506: ...IV 4 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 4 ...
Page 516: ...IV 14 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 14 ...
Page 533: ...IV 31 A CCESSORIES 4 Accessories 02 31 3 6 08 13 59 Page 31 ...
Page 534: ...DVM PLUS III V 2 05 1_control systems 002 045 3 15 08 4 09 Page 2 ...
Page 536: ...Control Systems V 4 05 1_control systems 002 045 3 15 08 4 09 Page 4 ...
Page 614: ...Control Systems V 82 05 3_control systems 082 141 3 6 08 14 03 Page 82 ...
Page 674: ...Control Systems V 142 05 4 6_control systems 142 171 3 6 08 14 09 Page 142 ...
Page 696: ...V 164 Control Systems 05 4 6_control systems 142 171 3 6 08 14 09 Page 164 ...
Page 703: ...V 171 C ONTROL S YSTEMS 05 4 6_control systems 142 171 3 6 08 14 09 Page 171 ...
Page 704: ...DVM PLUS III VI 2 06_Installation 02 45 3 15 08 4 34 Page 2 ...
Page 706: ...VI 4 Installation 06_Installation 02 45 3 15 08 4 34 Page 4 ...