VI
-7
I
NST
ALLA
TION
Oil trap
Allowable pipe length
from the first branch to
the farthest indoor unit
High pressure gas pipe
connection for HR
outdoor modules
(HR only)
New
additional joints
High pressure gas
connection for HR MCU
(HR only)
MCU
(HR system)
Additional refrigerant
charging
(HR system)
Maximum connectable
indoor units
64 indoor units
48 indoor units
Max. piping length
200m
90m
(If the pipe length between the first branch to the farthest indoor unit
is over 45 m, the pipe size has to be increased 1size.)
Y-joint (Optional products)
T-joint (Field available)
45m
-
-
-
170m
Interface module
MIM-B13A
MIM-B13
AVX
✳✳✳
000EE
AVX
✳✳✳
000EA, EB,EC
MCCB, ELB,
Power cable
Connectable indoor units
Ex) 12HP
Ex) 12HP
DVM PLUS
III
, DVM PLUS
III
HR
DVM PLUS
II,
DVM HR
II
•
When the piping length between the outdoor
units is 2m or more, a vertical trap has to be
installed like above diagram.
◆
High pressure gas pipe : brazing type
❈
Model: MXJ-YA1500/YA2500
MXJ-YA3100/YA3800
Less than 1m
200~300mm
No vertical trap
No vertical trap
2m or more
MCU-4EAE1
MCU-4EAEV1
MCU-6EAE1
◆
High pressure gas pipe : Flare type
MCU-4EAE
MCU-4EAEV
MCU-6EAE
Type
Model
Outdoor unit capacity
Outdoor joint
MXJ-T3100K
below 48HP
MXJ-T3800K
Above 50Hp
Type
Model
Outdoor joint
MXJ-T4422K
Y-joint
MXJ-YA2812K
Additional Refrigerant Charging of MCU Kit
(kg/unit)
Additional refrigerant charging of MCU is
0.5kg for every MCU kit.
0.5
HP
MCCB(A)
ELB
12
40
40A, 30mA, 0.1second or less
HP
MCCB(A)
ELB
12
35
40A, 30mA, 0.1second or less
❈
For more detail information about installation, refer to installation manual.
06_Installation(02~45) 3/15/08 4:34 Page 7
Summary of Contents for Mini DVM
Page 4: ...DVM PLUS III I 4 1 products 01 41 3 14 08 22 01 Page 4 ...
Page 42: ...DVM PLUS III II 2 chapter2_Indoor units 002 051 3 14 08 22 09 Page 2 ...
Page 44: ...II 4 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 4 ...
Page 64: ...Indoor Units II 24 chapter2_Indoor units 002 051 3 14 08 22 09 Page 24 ...
Page 76: ...II 36 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 36 ...
Page 110: ...II 70 Indoor Units chapter2_Indoor units 052 107 3 14 08 22 15 Page 70 ...
Page 183: ...II 143 I NDOOR U NITS chapter2_Indoor units 108 143 3 14 08 22 38 Page 143 ...
Page 184: ...DVM PLUS III III 2 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 2 ...
Page 186: ...Outdoor Units III 4 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 4 ...
Page 504: ...DVM PLUS III IV 2 4 Accessories 02 31 3 6 08 13 59 Page 2 ...
Page 506: ...IV 4 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 4 ...
Page 516: ...IV 14 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 14 ...
Page 533: ...IV 31 A CCESSORIES 4 Accessories 02 31 3 6 08 13 59 Page 31 ...
Page 534: ...DVM PLUS III V 2 05 1_control systems 002 045 3 15 08 4 09 Page 2 ...
Page 536: ...Control Systems V 4 05 1_control systems 002 045 3 15 08 4 09 Page 4 ...
Page 614: ...Control Systems V 82 05 3_control systems 082 141 3 6 08 14 03 Page 82 ...
Page 674: ...Control Systems V 142 05 4 6_control systems 142 171 3 6 08 14 09 Page 142 ...
Page 696: ...V 164 Control Systems 05 4 6_control systems 142 171 3 6 08 14 09 Page 164 ...
Page 703: ...V 171 C ONTROL S YSTEMS 05 4 6_control systems 142 171 3 6 08 14 09 Page 171 ...
Page 704: ...DVM PLUS III VI 2 06_Installation 02 45 3 15 08 4 34 Page 2 ...
Page 706: ...VI 4 Installation 06_Installation 02 45 3 15 08 4 34 Page 4 ...