14-3-3 Vacuum Preparing Operation
■
Oil recovery in the heating
■
Make the condition of the outdoor unit vacuum preparing operation
1.
Purpose :
According to the valves such as EEV, Solenoid Valve, and Check Valve, the vacuum and the emission of refrigerant may not be
succeeded smoothly. Therefore, insert a separate operation mode for the vacuum or the complete emission of refrigerant.
2. Use the K1 key
3. Determine an operation outdoor unit
The number of pressing
Display
8 times: Main unit
8 times:
9 times: Sub1 unit
9 times:
10 times: Sub2 unit
10 times:
11 times: Sub3 unit
11 times:
12 times: All unit
12 times:
4.
Operation Method :
All the EEV of the outdoor unit on the vacuum mode is opened to the maximum degree of openness and all the Solenoid Valve is
waited on the open state.
1. This is an operation mode to recover compressor oil that moved to pipe or indoor unit after mixing with refrigerant during opera-
tion.
2. Use the K1 Key
3. Automatic operation by the basic setting time during heating operation
4. Use the key mode if required
The number of pressing
Display
7 times : MAIN
7 times:
Sub3
Sub2
Sub1
Main
Sub3
Sub2
Sub1
Main
Summary of Contents for mini DVM Series
Page 48: ...MEMO 2 38 Samsung Electronics ...
Page 174: ...MEMO 5 36 Samsung Electronics ...
Page 180: ...MEMO 5 42 Samsung Electronics ...
Page 184: ...MEMO 5 46 Samsung Electronics ...
Page 188: ...MEMO 5 50 Samsung Electronics ...
Page 192: ...MEMO 5 54 Samsung Electronics ...
Page 484: ...MEMO 12 73 Samsung Electronics ...
Page 514: ...14 18 Samsung Electronics Reference Information Thermodynamic characteristic of R410A ...
Page 520: ...MEMO 14 24 Samsung Electronics ...
Page 521: ...MEMO Samsung Electronics 14 25 ...