• Selecting additional refrigerant charge
- Depends on the total length of the liquid side pipe.
- Example of calculating additional refrigerant:In case of 30HP outdoor unit
- The amount of basic charge
Liquid side pipe ø22.23
Total pipe length(m)X 0.35
a : ø19.05x30m
b : ø15.88x10m
c : ø9.52x10m
d : ø9.52x10m
e : ø9.52x10m
f : ø9.52x10m
g : ø6.35x10m
h : ø6.35x10m
i : ø12.70x10m
j : ø6.35x10m
k : ø6.35 x 9m
Liquid side pipe ø19.05
Total pipe length(m)X 0.27
Liquid side pipe ø15.88
Total pipe length(m)X 0.18
A =
A =
+
+
+
+
= 14.33
30x0.27
10x0.18
10x0.125
40x0.06
39x0.02
+
+
+
Liquid side pipe ø12.70
Total pipe length(m)X 0.125
Liquid side pipe ø9.52
Total pipe length(m)X 0.06
Liquid side pipe ø6.35
Total pipe length(m)X 0.02
+
+
Pipe diameter (mm)
ø22.23
ø19.05
ø15.88
ø12.70
ø9.52
ø6.35
Total length (m)
0
30
10
10
40
39
HP
Factory charged (kg)
8/10
6.3
12/14
7.5
Liquid side pipe (mm)
Basic charging for pipes (kg)
ø6.35
0.02
ø9.52
0.06
ø12.70
0.125
ø15.88
0.18
ø19.05
0.27
ø22.23
0.35
Summary of Contents for mini DVM Series
Page 48: ...MEMO 2 38 Samsung Electronics ...
Page 174: ...MEMO 5 36 Samsung Electronics ...
Page 180: ...MEMO 5 42 Samsung Electronics ...
Page 184: ...MEMO 5 46 Samsung Electronics ...
Page 188: ...MEMO 5 50 Samsung Electronics ...
Page 192: ...MEMO 5 54 Samsung Electronics ...
Page 484: ...MEMO 12 73 Samsung Electronics ...
Page 514: ...14 18 Samsung Electronics Reference Information Thermodynamic characteristic of R410A ...
Page 520: ...MEMO 14 24 Samsung Electronics ...
Page 521: ...MEMO Samsung Electronics 14 25 ...