6. Remove the front protective film.
• When installing a Wired Remote Controller by using a cable longer than 10 m, you must install the
communication cable and the power cable separately. (Electrical interference can cause the Wired Remote
Controller to malfunction.)
• When installing your Wired Remote Controller on the wall, consider the size of the wire hole, and select a wire
with a proper thickness.
• Wire that is connectable to Wired Remote Controller PCB.
- If you install the Wired Remote Controller by reclaiming, install it according to U-terminal cable specification.
- If you install the Wired Remote Controller by using two pieces of PVC wire, remove the 30 cm of the sheath of
the cable and install it only with the two pieces of wires. (Recommended specification: AWG20)
• The following are the specs of the compression ring terminal connected to your Wired Remote Controller PCB.
Stud
W
t
E
F
G
L
ØD
Range of Permitted Wires
Rated Size
Stud Size
Basic Size (mm)
AWG
mm
2
mm
2
mm
t
øD
G
E
F
W
L
22 ~ 16
0.25 ~ 1.65
1.5
3
0.7
3.8
10.0
4.5
6.5
6.0
21.2
❋
Maximum distance for connecting communication and power cable: 100 m
• Screws on the PCB terminal must be tightened with less than 6N-cm tightening torque. If the tightening torque
is greater, it may damage the screw thread.
CAUTION
9
ENGLISH