63
ENGLISH
Main
menu
Sub
menu
Function
Data
bit
Factory
setting
Description
Unit
1
1
Wireless remote controller
Option setting/checking (1)
Cooling/Heating selection
1
0
0 – Cooling/Heating,
1 – Cooling only
-
Use of wireless remote controller
2
1
0 – No use, 1 - Use
-
MAIN/SUB wired remote
controller
3
0
0 –MAIN, 1- SUB
-
Temperature unit
4
0
0 – Celcius(°C), 1 – Fahrenheit(°F)
-
2
Wireless remote controller
Option setting/checking (2)
Temperature sensor selection
1
0
0 – Indoor unit,
1 – Wired remote controller
-
Use of average temperature
2
0
0 – No use, 1 - Use
-
Use of Auto mode
3
1
0 – No use, 1 - Use
-
Temperature display
4
0
0 – Set temperature,
1 - Room temperature
-
AC On/Off button function
5
0
o*OEPPSVOJU&37
1 – Indoor unit only,
o&37POMZ
-
3
Blade
setting/checking
Lock of Blade1
1
0
0 – Unlock, 1 – lock
-
Lock of Blade2
2
0
0 – Unlock, 1 – lock
-
Lock of Blade3
3
0
0 – Unlock, 1 – lock
-
Lock of Blade4
4
0
0 – Unlock, 1 – lock
-
4
&37PQUJPO
Setting/checking
Use of By-Pass mode
1
0
0 – No use, 1 - Use
-
Use of Auto mode
2
0
0 – No use, 1 - Use
-
Use of air purification mode
3
0
0 – No use, 1 - Use
-
Use of external control
4
0
0 – No use, 1 - Use
-
5
Room Temperature
compensation
Temperature control reference
1,2,3
0
-9 ~ 40 °C(15~104 °F)
0.1 °C
Temperature compensation value
4,5,6
0
-9.9 ~ 9.9 °C
0.1 °C
6
Number of connected units
Number of indoor units
1,2
-
0 ~ 16
-
/VNCFSPG&37T
3,4
-
0 ~ 16
-
7
Temperature increment/decrement (°C only)
1
0
0-1 °C, 1-0.5 °C, 2-0.1 °C
-
8
4FU$IFDL&37&OFSHZTBWJOH
operation
Select individual Energy saving
operation
1
0
0-ON/OFF alternating operation,
1-Outdoor air cooling operation
for different temperature setting
-
Minimum temperature of
outdoor air cooling
3,4
15
5 ~ 15 °C (41~59 °F)
°C
0
Factory option setting
1
0
0 – Unchanged
1 – Factory setting
-
2
1
Software code
1~6
-
Software code
-
2
Software version
1~6
-
Software version
-
Additional Functions of Your Wired Remote Controller
t A/0/&XJMMCFEJTQMBZFEJGUIFJOEPPSVOJUEPFTOPUTVQQPSUUIFGVODUJPO
In some cases, the setting may not possible or it may be not applied though it is set on the unit.
t *GDPNNVOJDBUJPOJOJUJBMJ[BUJPOJTOFFEFEBGUFSUIFTFUUJOHUIFTZTUFNXJMMSFTFUBVUPNBUJDBMMZBOE
communication will be initialized.
Wired Remote Controller Installation/Service Mode