31
AA
The following accessories are supplied with the indoor unit.
The type and quantity may differ depending on the specifications.
Accessories
User & Installation
manual
Insulation cover
pipe in
Insulation cover
pipe out
Insulation drain
Insulation cover
drain
Insulation pipe
Cable tie
Flexible hose
Clamp hose
Selecting the installation location
X
There must be no obstacles near the air inlet and outlet.
X
Install the indoor unit on a ceiling that can support its weight.
X
Maintain sufficient clearance around the indoor unit.
X
Make sure that the water dripping from the drain hose runs away correctly and safely.
X
The indoor unit must be installed in this way, that they are out of public access. (Not touchable by the users)
X
After connecting a chamber, insulate the connection part between the indoor unit and the chamber with t10 or thicker
insulation. Otherwise, there can be air leak or dew from the connection part.
X
Rigid wall without vibration.
X
Where it is not exposed to direct sunshine.
X
Where the replacement parts. (air filter, heat exchange element) can be removed and cleaned easily.
Space Requirements
Model
'A'
'B'
'C'
'D'
'E'
AM050FNKDEH
1000
1553
600
200
450 x 450 or more
AM100FNKDEH
1135
1763
800
300
550 x 550 or more
Inspection hole('E'mm)
GPS%9$0*-
Inspection hole('E'mm)
for filter, heat exchange element, fan,
motor and damper
'B' mm
'A' mm
'D' mm
Return Air
Exhaust Air
Supply Air
Outdoor Air
'C' mm
ENGLISH