Field specification setting mode
1. Hydro unit
Classification
Function
Detail
Code
(Main
+ sub
menu)
Basic Min.
Max.
Step
Unit
Remote
controller
Temperature of general cooling
leaving water
Max.
1011
25
18
25
1
°C
Min.
1012
16
5
18
1
°C
General indoor cooling temperature
Max.
1021
30
28
30
1
°C
Min.
1022
18
18
28
1
°C
Temperature of general heating
leaving water
Max.
1031
50
37
50
1
°C
Min.
1032
25
15
37
1
°C
General indoor heating temperature
Max.
1041
30
18
30
1
°C
Min.
1042
16
16
18
1
°C
Temperature of hot water tank
Max.
1051
50
40
75
1
°C
Min.
1052
35
30
40
1
°C
Water Law
Auto heating ambient temperature
Max.
2011
-10
-20
5
1
°C
Min.
2012
15
10
20
1
°C
Temperature of auto heating
leaving water (WL1-Floor)
Max.
2021
45
35
50
1
°C
Min.
2022
30
17
37
1
°C
Temperature of auto heating
leaving water (WL2-FCU)
Max.
2031
50
35
50
1
°C
Min.
2032
35
17
50
1
°C
Auto heating of wired remote
controller
WL type
2041 1(WL1)
1
2
-
-
Use of thermostat
-
2091
0(No)
0
2
-
-
DHW
Activating hot water function
DHW application
3011
0(No)
0
1(Yes)
-
-
Heating mode
Max.
3021
50
45
50
1
°C
Stop
3022
2
0
10
1
°C
Start
3023
5
5
20
1
°C
Minimum heating
operation time
3024
5
1
20
1
min.
DHW operation time
3025
30
5
95
5
min.
Heating operation
time
3026
3
0.5
10
0.5
hour
Booster heater
Operation
3031
1 (On) 0 (Off)
1
-
-
Delayed time
3032
20
20
95
5
min.
Overshoot
3033
0
0
4
1
°C
Disinfection
Operation
3041
1 (Yes) 0 (No)
1
-
-
Operation interval
3042
Fri(5) Sun(0) AllDay(7)
-
day
Start time
3043
23
0
23
1
hour
Target temp.
3044
70
40
70
5
°C
Holding time
3045
10
5
60
5
min.
Max. operation time
3046
8
1
24
1
hour
Solar heat panel / defrost signal
Solar heat panel
H/P interlocking /
defrost signal
3061
0
0
3
-
-