26
•
3041: Application of disinfection function
•
3042: Scheduling (day)
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
AllDay
0
1
2
3
4
5
6
7
•
3043: Starting time (hour)
•
3044: Target tank temp
•
3045: Duration time (After reaching the target temperature)
•
3046: Maximum duration of disinfection operation (disinfection operation stops after the specified duration)
❋
❋
Disinfection operation can start if a booster heater is connected.
❋
❋
Check the booster heater capacity and booster heater failure , if disinfection operation does not work normally
over the maximum duration. (E919 error)
•
3061: Interlock between solar pump and hot water
- 0: Hydro unit ‘s operation regardless of solar pump activation
- 1: Hydro unit’s stop when solar pump is operating
- 2: Disabled
- 3: Defrost signal output when entering defrost mode
f
f
Code 401*
- Space/DHW heating priority and control variables
•
4011 : Priority setting of simultaneous operation both hot water and heating
- 0: Hot water operation has priority. (The related operation is followed with 302*)
- 1: Heating operation has priority. (If an ambient temperature < 4012, hot water operation is neglected.)
•
4012 : The temperature of forced heating priority (Refer to 4011)
•
4013 : If the ambient temperature > 4013, Heating Mode stops in auto mode.
f
f
Code 50**
- User’s options for extra functions
501*: New target temperatures of each mode (Heating/Cooling/DHW) when “Outing” function is on
•
5011: Value of cooling leaving water temperature setting when “Outing” function is on
•
5012: Value of cooling indoor’s room temperature setting when”Outing” function is on
•
5013: Value of heating leaving water temperature setting when “Outing” function is on
•
5014: Value of heating indoor’s room temperature setting when”Outing” function is on
•
5017: Value of Water Law’s floor control (#2041=1) leaving water temperature setting when “Outing” function is on
•
5018: Value of Water Law’s FCU control (#2041=2) leaving water temperature setting when “Outing” function is on
•
5019: Value of DHW tank’s temperature setting
5021: Offset temperature setting when Economic DHW operation is on (During Economic DHW operation, temperature
will be automatically set lower by value of #5021(°C) than actual setting)
504*: Smart Grid control
•
5041: Application of Smart Grid control
•
5042: Heater application during Smart Grid control
- 0: Heater off during Smart Grid control
- 1: Heater control during Smart Grid control
- 2: Not use
•
5043: Input Voltage from Smart Grid contact port
- 0: If Smart Grid Voltage = 0V, Smart Grid Control is Operated
- 1: If Smart Grid Voltage = 5V, Smart Grid Control is Operated
•
5061: Water supply capacity ratio compared to heating: The load of hot water tank if designed heating (floor or Fan
coil unit) load is 7
ex) When required heating load is 14000W, required hot water tank load 10000W, 10000/14000x7= Set 5
Field specification setting mode of wired remote controller