10. Installation
Refrigerant pipe installation
f
Amount of additional refrigerant for each indoor unit (
ⓑ
)
(Unit : kg)
Capacity (kW)
Model
1 .5 1 .7 2 .2 2 .8 3 .2 3 .6 4 .5 5 .6 6
7 .1 8 .2 9
9.3 11 .2 12 .8 14 16 18 22 22 .4 28 32 50 500
CMH
1000
CMH
Slim 1way cassette (JSF)
(AM∗∗∗FN1DE∗∗)
(AM∗∗∗JN1DE∗∗)
0 .25 0 .25
0 .25
0 .32
0 .32
Interior 1way cassette
(AM∗∗∗HN1DE∗∗)
0 .15 0 .15
2way cassette
(AM∗∗∗FN2DE∗∗)
0 .31
0 .47
4Way Casette S
(AM∗∗∗FN4DE∗∗)
0 .45 0 .45
0 .45
0 .45
0 .57 0 .69 0 .69
360 Casette
(AM∗∗∗KN4DE∗∗)
0 .45 0 .45
0 .45
0 .45
0 .69 0 .69 0 .69
Floor Standing Unit
(AM∗∗∗∗NFDE∗∗)
0 .22
0 .32
0 .32
ERV plus (AM∗∗∗FNKDE∗∗)
0 .11 0 .36
4way cassette S (600 ⅹ 600)
(AM∗∗∗FNNDE∗∗)
0 .29
0 .29 0 .29
0 .29 0 .37 0 .37 0 .37
Duct S (AM∗∗∗HNMPK∗/∗)
0 .22 0 .22 0 .22
0 .22
0 .31
0 .38 0 .38 0 .38
Duct S (AM∗∗∗HNMPK∗9∗)
0 .31 0 .31 0 .38 0 .38
0 .38
Duct S (AM∗∗∗HNHPK∗/∗)
0 .38 0 .38 0 .38
Slim duct (AM∗∗∗FNLDE∗∗)
0 .17 0 .17 0 .17
0 .26 0 .35 0 .35
0 .45
0 .42
0 .42 0 .62 0 .62
Slim duct (with drain pump)
(AM∗∗∗KNLDE∗∗)
0 .35 0 .35
0 .45
0 .42
0 .42 0 .62 0 .62
MSP duct
(AM∗∗∗∗NMDE∗∗)
0 .24 0 .24
0 .24 0 .28 0 .28
0 .28
0 .32
0 .54 0 .68 0 .68 0 .91
MSP duct (with drain pump)
(AM∗∗∗KNMDE∗∗)
0 .24 0 .24
0 .24 0 .28 0 .28
0 .28
0 .32
0 .54 0 .68 0 .68 0 .91
Home Duct (AM∗∗∗KNLDEH)
0.13 0.13 0.13
0.17
Ceiling (AM∗∗∗FNCDE∗∗ /
AM∗∗∗JNCDK∗∗)
0 .39
0 .39
0 .56
0 .95
Console (AM∗∗∗∗NJDE∗∗)
0 .16 0 .27
0 .27 0 .27 0 .27
Neo forte (AM∗∗∗FNTDE∗∗)
0 .24
0 .24 0 .24
0 .24
0 .36
0 .36
Neo forte (with EEV)
(AM∗∗∗FNQDE∗∗)
0 .34
0 .34 0 .34
0 .34 0 .51 0 .51
0 .51
AR5000 (AM∗∗∗JNADK∗∗)
0 .16
0 .16 0 .19
0 .25 0 .25 0 .52
0 .52 0 .52
AR5000 (with EEV)
(AM∗∗∗JNVDK∗∗)
0 .22
0 .22 0 .25
0 .34 0 .34 0 .71
0 .71 0 .71
New Boracay
(AM∗∗∗KNTDE∗∗)
0.24
0.24 0.32
0.32 0.49 0.49
0.49
New Boracay (with EEV)
(AM∗∗∗KNQDE∗∗)
0.24
0.24 0.32
0.32 0.49 0.49
0.49
MAX 4 (with EEV)
(AM∗∗∗MNQDE∗∗)
0.49
HSP duct (AM∗∗∗FNHDE∗∗)
0 .68 0 .68 0 .68
1 .18
1 .18
OAP duct (AM∗∗∗JNEPE∗∗)
0 .68
1 .18
1 .18
Big duct (AM∗∗∗JNHFK∗∗)
1 .15
1 .15
Hydro Unit HE
(AM∗∗∗FNBD∗∗)
0.6
0.7 1.2
Hydro Unit HT
(AM∗∗∗FNBF∗∗)
0.6
note1)
MCU (MCU-S∗NE∗∗N)
0.5
f
If AHU kit is included among the indoor units, you must add 0.063kg of refrigerant for every 1kW of the AHU
capacity increase.
Note1)
In case the capacity conjunction of the Hydro Unit HT exceeds 50 % among the total indoor unit, please don’t put
the additional refrigerant.