background image

31

7. Sound Data

Sound Pressure level

Unit: dB(A)

Microphone

Front

1m

1.5m

Model

Cooling Silent 1 Silent 2 Silent 3

AM100MXVDGH/ET

58

55

52

49

AM120MXVDGH/ET

62

55

52

49

AM140MXVDGH/ET

61

57

55

49

AM160MXVDGH/ET

63

59

56

49

 

• NR Curve

1)  AM100MXVDGH/ET

2) AM120MXVDGH/ET

T

E

/

H

G

D

V

X

M

0

0

1

M

A

NR 65
NR 60
NR 55
NR 50
NR 45
NR 40
NR 35
NR 30
NR 25
NR 20
NR 15

Hearing 

threshold

Cooling

Silent 1

Silent 2
Silent 3

NR 90
NR 85

NR 80
NR 75
NR 70

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

63

125

250

500

1000

2000

4000

8000

So

un

Pr

ess

ur

Le

ve

l (

dB

)

Octave Band Center Frequency(Hz)

T

E

/

H

G

D

V

X

M

0

2

1

M

A

NR 65
NR 60
NR 55
NR 50
NR 45
NR 40
NR 35
NR 30
NR 25
NR 20
NR 15

Hearing 

threshold

Cooling

Silent 1

Silent 2
Silent 3

NR 90
NR 85

NR 80
NR 75
NR 70

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

63

125

250

500

1000

2000

4000

8000

So

un

Pr

es

su

re

 L

ev

el

 (d

B)

Octave Band Center Frequency(Hz)

3) AM140MXVDGH/ET

4) AM160MXVDGH/ET

T

E

/

H

G

D

V

X

M

0

4

1

M

A

NR 65
NR 60
NR 55
NR 50
NR 45
NR 40
NR 35
NR 30
NR 25
NR 20
NR 15

Hearing 

threshold

Cooling

Silent 1

Silent 2
Silent 3

NR 90
NR 85

NR 80
NR 75
NR 70

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

63

125

250

500

1000

2000

4000

8000

So

un

Pr

es

su

re

 L

ev

el

 (d

B)

Octave Band Center Frequency(Hz)

T

E

/

H

G

D

V

X

M

0

6

1

M

A

NR 65
NR 60
NR 55
NR 50
NR 45
NR 40
NR 35
NR 30
NR 25
NR 20
NR 15

Hearing 

threshold

Cooling

Silent 1

Silent 2
Silent 3

NR 90
NR 85

NR 80
NR 75
NR 70

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

63

125

250

500

1000

2000

4000

8000

So

un

Pr

es

su

re

 L

ev

el

 (d

B)

Octave Band Center Frequency(Hz)

 NOTE

 

• Specifications may be subject to change without prior notice.

 - Sound pressure level is obtained in an anechoic room.
 - Sound pressure level is a relative value, depending on the distance and acoustic environment.
 - Sound pressure level may differ depending on operation condition.
 - dBA = A-weighted sound pressure level
 -

Reference acoustic pressure 0 dB = 20μPa

Summary of Contents for DVM S AM100MXVDGH/ET

Page 1: ...Model Essential Type VRF Technical Data Book DVM S forEuro_ET R410A 50Hz HP ...

Page 2: ... 2 History Version Modification Date Remark Ver 1 0 Release DVM S Essential R410A 50Hz HP for Euro_ET TDB 16 12 19 ...

Page 3: ...it 5 Feature 1 V Inverter M DVM S Eco 6 Feature 2 A Standard General Temp Module H High EER Low Temp Module G High EER General Temp Module D Standard General Temp Non Module 7 Rating Voltage E 1Ø 220 240V 50Hz G 3Ø 380 415V 50Hz N 3Ø 380 415V 50 60Hz 8 Mode H Heat Pump R Heat Recovery Nomenclature OutdoorUnit Model Name 1 2 3 4 5 6 7 8 Buyer ...

Page 4: ...sung DVM S offers innovative features to benefit the indoor comfort as well operational coasts of the system through technological advances such as The world s largest capacity Capacities of the outdoor units offer up to 30 HP rooftop space savings as well as lowering the installations and transportation costs High seasonal energy efficiency Samsung DVM S adopts a dual inverter scroll compressor t...

Page 5: ...ended Piping Length Limits Allows extended piping length of up to 220 m and units will still give a great performance overwide areas With this technology installation is available with a maximum height level of 110 m which is equivalent to 20 stories each story is considered 5 m high Smart management Further improves system s energy efficiency due to precise indoor climate control Web based remote...

Page 6: ...Table 7 2 Specification 11 3 Electric Characteristics 23 4 Dimensional Drawing 24 5 Center of Gravity 26 6 Electrical Wiring Diagrams 28 7 Sound Data 30 8 Operation Range 35 9 Piping Diagram 37 10 Installation 41 11 Accessory 77 ...

Page 7: ...If the total capacity of the connected indoor units exceeds the indicated maximum capacity cooling and heating capacity of the indoor unit may decrease Total capacity of the connected indoorunits can be allowed from 50 to130 of the total outdoorunit capacity 0 5 Σ Outdoorunit capacity Total capacity of the connected indoorunits 1 3 Σ Outdoorunit capacity You can connect maximum 64 indoorunits to t...

Page 8: ... 2 8 3 2 3 6 4 5 5 6 6 0 7 1 8 2 9 0 11 2 12 8 14 0 16 0 1Way CST JSF 0 JSF 1 JSF 2 2Way CST 4Way CST 360 CST Floor Standing Unit 4Way CSTS 600X600 Duct S MSP Slim Duct MSP Duct Ceiling Console Boracay Boracay with EEV AR5000 AR5000 with EEV IndoorUnits ...

Page 9: ...decrease Total capacity of the connected indoor units can be allowed from 50 to 130 of the total outdoor unit capacity 0 5 Σ Outdoor unit capacity Total capacity of the connected indoor units 1 3 Σ Outdoor unit capacity You can connect maximum 64 indoorunits to the outdoorunit Maximum quantity of connectable indoorunit is set to 64 since outdoorunit only support up to 64 communication address Indo...

Page 10: ...MXVDGH ET AM120MXVDGH ET 14 16 18 AM140MXVDGH ET AM160MXVDGH ET AM180MXVDGH ET 20 22 24 AM200MXVDGH ET AM220MXVDGH ET AM240MXVDGH ET 26 30 AM260MXVDGH ET AM300MXVDGH ET 28 32 34 36 AM280MXVDGH ET AM320MXVDGH ET AM340MXVDGH ET AM360MXVDGH ET 38 AM380MXVDGH ET 40 AM400MXVDGH ET External Appearance ...

Page 11: ...e Heat Exchanger Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu FinTreatment Anti corrosion Anti corrosion Anti corrosion Compressor Output kWxn 6 39 x1 6 39 x1 6 39 x1 ModelName DS GB066FAV x1 DS GB066FAV x1 DS GB066FAV x1 Oil Type PVE PVE PVE Initialcharge ccxn 1 100 x1 1 100 x1 1 100 x1 Fan Type Propeller Propeller Propeller Dischargedirection Top Top Top Quantity EA 1 1 2 ...

Page 12: ...Outdoor temperature 7 C DB 6 C WB Eurovent certified 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound...

Page 13: ...Type Fin Tube Fin Tube Fin Tube Material Fin Al Al Al Tube Cu Cu Cu FinTreatment Anti corrosion Anti corrosion Anti corrosion Compressor Output kWxn 7 81 x1 7 81 x1 6 39 x1 x 2 ModelName DS4GJ5080FV x1 DS4GJ5080FV x1 DS GB066FAV x1 x 2 Oil Type PVE PVE PVE Initialcharge ccxn 1 400 x1 1 400 x1 1 100 x1 x 2 Fan Type Propeller Propeller Propeller Dischargedirection Top Top Top Quantity EA 2 2 2 AirFl...

Page 14: ...emperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB Eurovent certified 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation con...

Page 15: ...ube Cu Cu Cu FinTreatment Anti corrosion Anti corrosion Anti corrosion Compressor Output kWxn 6 39 x1 x 2 6 39 x1 x 2 6 39 x1 x 2 ModelName DS GB066FAV x1 x 2 DS GB066FAV x1 x 2 DS GB066FAV x1 x 2 Oil Type PVE PVE PVE Initialcharge ccxn 1 100 x1 x 2 1 100 x1 x 2 1 100 x1 x 2 Fan Type Propeller Propeller Propeller Dischargedirection Top Top Top Quantity EA 2 2 3 AirFlowRate m3 min 170 x1 220 x1 220...

Page 16: ...g Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB Eurovent certified 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the dis...

Page 17: ...sion Anti corrosion Anti corrosion Compressor Output kWxn 6 39 x1 x 2 6 39 x1 x1 7 81 x1 x1 6 39 x1 x1 7 81 x1 x1 ModelName DS GB066FAV x1 x 2 DS GB066FAV x1 x1 DS4GJ5080FV x1 x1 DS GB066FAV x1 x1 DS4GJ5080FV x1 x1 Oil Type PVE PVE PVE Initialcharge ccxn 1 100 x1 x 2 1 100 x1 x1 1 400 x1 x1 1 100 x1 x1 1 400 x1 x1 Fan Type Propeller Propeller Propeller Dischargedirection Top Top Top Quantity EA 4 ...

Page 18: ...oling Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB Eurovent certified 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the...

Page 19: ...ype Fin Tube Fin Tube Material Fin Al Al Tube Cu Cu FinTreatment Anti corrosion Anti corrosion Compressor Output kWxn 7 81 x1 x 2 7 81 x1 x 2 ModelName DS4GJ5080FV x1 x 2 DS4GJ5080FV x1 x 2 Oil Type PVE PVE Initialcharge ccxn 1 400 x1 x 2 1 400 x1 x 2 Fan Type Propeller Propeller Dischargedirection Top Top Quantity EA 4 4 AirFlowRate m3 min 255 x1 290 x1 290 x 2 l s 4 250 x1 4 833 x1 4 833 x 2 Ext...

Page 20: ...r temperature 7 C DB 6 C WB Eurovent certified 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation condition dBA A weighted sound press...

Page 21: ... Fin Tube Fin Tube Material Fin Al Al Tube Cu Cu FinTreatment Anti corrosion Anti corrosion Compressor Output kWxn 6 39 x1 x 3 6 39 x1 x 3 ModelName DS GB066FAV x1 x 3 DS GB066FAV x1 x 3 Oil Type PVE PVE Initialcharge ccxn 1 100 x1 x 3 1 100 x1 x 3 Fan Type Propeller Propeller Dischargedirection Top Top Quantity EA 4 5 AirFlowRate m3 min 220 x 2 255 x1 220 x1 255 x 2 l s 3 667 x 2 4 250 x1 3 667 x...

Page 22: ...rature 35 C DB 24 C WB Heating Indoor temperature 20 C DB 15 C WB Outdoor temperature 7 C DB 6 C WB Eurovent certified 2 Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 3 Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure leve...

Page 23: ... 2 63 1 66 4 8 22 61 6 AM220MXVDGH ET 50 380 415 342 456 26 5 26 8 46 1 63 1 66 4 8 24 67 2 AM240MXVDGH ET 50 380 415 342 456 30 29 6 50 63 1 66 4 8 26 73 6 AM260MXVDGH ET 50 380 415 342 456 34 9 32 7 50 63 2 07 6 2 28 80 0 AM280MXVDGH ET 50 380 415 342 456 39 8 35 8 50 63 2 48 7 6 30 84 0 AM300MXVDGH ET 50 380 415 342 456 40 7 38 5 64 2 75 2 07 6 2 32 90 4 AM320MXVDGH ET 50 380 415 342 456 45 6 4...

Page 24: ... descriptions Remark 1 Gas Ref pipe See note 4 5 Powerwiring conduit Φ44 2 Liquid Ref pipe See note 4 6 Communication wiring conduit Φ22 3 Powerwiring conduit Φ44 7 Knock out Hole for Ref Piping bottom 4 Communication wiring conduit Φ34 8 Knock out Hole for Ref Piping front Outdoorunit ...

Page 25: ... descriptions Remark 1 Gas Ref pipe See note 4 5 Powerwiring conduit Φ44 2 Liquid Ref pipe See note 4 6 Communication wiring conduit Φ22 3 Powerwiring conduit Φ44 7 Knock out Hole for Ref Piping bottom 4 Communication wiring conduit Φ34 8 Knock out Hole for Ref Piping front Outdoorunit ...

Page 26: ...y 26 5 Centerof Gravity AM100 120MXVDGH 761 2 6 740 2 5 1695 5 6 3 4 A C B Units mm inches Model A B C AM080 360 1 2 1 4 455 1 6 560 1 10 AM100 360 1 2 1 4 455 1 6 560 1 10 AM120 360 1 2 1 4 455 1 6 560 1 10 Outdoorunit ...

Page 27: ... Gravity Outdoorunit AM140 180MXVDGH 1695 5 6 3 4 761 2 6 1150 3 9 1 4 B A C Units mm inches Model A B C AM140 370 1 2 1 2 595 1 11 620 2 4 AM160 365 1 2 3 8 655 2 1 3 4 620 2 4 AM180 365 1 2 3 8 655 2 1 3 4 620 2 4 ...

Page 28: ... Solenoid valve Main cooling COMP1 Motor compressor1 OIL COMP2 Oil Sensor Compressor2 HOTGAS2V V Solenoid valve Hot Gas Bypass2 COMP2 Motor compressor2 OUT 10K Thermistor Ambient Temp _10Kohm OD EEVV V Solenoid valve OutdoorEEV FAN1 Motor fan1 COND 10K Thermistor Cond Out Temp _10Kohm F101 FUSE InverterPBA FAN2 Motor fan2 TOP1 200K Thermistor CompressorTop1_200Kohm 690V T40A FUSE EMI PBA EVIV V1 S...

Page 29: ... Solenoid valve Main cooling COMP1 Motor compressor1 OIL COMP2 Oil Sensor Compressor2 HOTGAS2V V Solenoid valve Hot Gas Bypass2 COMP2 Motor compressor2 OUT 10K Thermistor Ambient Temp _10Kohm OD EEVV V Solenoid valve OutdoorEEV FAN1 Motor fan1 COND 10K Thermistor Cond Out Temp _10Kohm F101 FUSE InverterPBA FAN2 Motor fan2 TOP1 200K Thermistor CompressorTop1_200Kohm 690V T56A FUSE EMI PBA EVIV V1 S...

Page 30: ...66 69 86 32 90 4 AM320MXVDGH ET 66 68 86 34 95 4 AM340MXVDGH ET 67 70 87 36 100 8 AM360MXVDGH ET 67 70 87 38 107 2 AM380MXVDGH ET 66 68 86 40 113 6 AM400MXVDGH ET 66 68 86 NOTE Sound Pressure Level Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environment Sound pressure level may differ depending on operation co...

Page 31: ...evel dB Octave Band Center Frequency Hz 3 AM140MXVDGH ET 4 AM160MXVDGH ET T E H G D V X M 0 4 1 M A NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 25 NR 20 NR 15 Hearing threshold Cooling Silent 1 Silent 2 Silent 3 NR 90 NR 85 NR 80 NR 75 NR 70 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 63 125 250 500 1000 2000 4000 8000 Sound ...

Page 32: ...20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 63 125 250 500 1000 2000 4000 8000 Sound Pressure Level dB Octave Band Center Frequency Hz NOTE Specifications may be subject to change without prior notice Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and acoustic environmen...

Page 33: ...A Sound Power Level dB Octave Band Center Frequency Hz 3 AM140MXVDGH ET 4 AM160MXVDGH ET T E H G D V X M 0 4 1 M A NR 90 NR 85 NR 80 NR 75 NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 25 NR 20 NR 15 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 125 250 500 1000 2000 4000 8000 A Sound Power Lev...

Page 34: ... 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 125 250 500 1000 2000 4000 8000 A Sound Power Level dB Octave Band Center Frequency Hz NOTE Specifications may be subject to change without prior notice Sound power level is an absolute value that a sound source generates dBA A weighted sound power level Reference power 1pW Measur...

Page 35: ...ration Range 1 The operating range is shown in these figures 2 The assumed installation condtions are as follows Outdoor units and indoor units combination The Pipe length including elbow is 5m The Level difference is 0m 3 In the low temperature expansion option application the cooling operating is possible under expand operational range only for HR system 4 In case of heatlng mode operating is po...

Page 36: ...4 2 0 2 5 7 Capacity coefficient Outdoor temperature C Capacity coefficient of outdoor unit on defrost operation 0 99 0 98 0 96 0 95 0 91 0 88 0 86 0 91 1 00 On heating operation frost can be formed on heat exchanger according to outdoor temperature Frost on heat exchanger results in decreasing the performance To remove frost on heat exchanger of outdoor unit defrost operation is carried out periodi...

Page 37: ...iquidpipe BV_L SolenoidValve AccumulatoroilReturn V_AR SolenoidValve HotGasbypass V_HG Compressor COMP Thermistor Discharge pipe T_D SolenoidValve 4Way V_4W Accumulator AC Thermistor Suctionpipe T_S Thermistor Ambient T_A Thermistor CondOut T_CO Electronic Expansion Valve Main E_M Check Valve EEV Bypass CV_EB Pressure Sensor Low PS_L Heat Exchanger Main HX_M OilSeparator OS Pressure Sensor High PS...

Page 38: ... Liquidpipe BV_L SolenoidValve AccumulatoroilReturn V_AR SolenoidValve HotGasbypass V_HG Compressor COMP Thermistor Discharge pipe T_D OilSeparator OS Pressure Sensor High PS_H SolenoidValve 4Way V_4W Thermistor Compressor Top T_CT CheckValve Discharge CV_D Accumulator AC Thermistor Suctionpipe T_S Pressure Sensor Low PS_L Pressure Switch High PW_H Thermistor Ambient T_A Thermistor Cond Out T_CO E...

Page 39: ...ermistor EVI Out T_EO Solenoid Valve EVI Bypass V_EB Ball Valve Liquid pipe BV_L Solenoid Valve Accumulator oil Return V_AR Solenoid Valve Hot Gas bypass V_HG Solenoid Valve EVI V_EVI Compressor COMP Thermistor Discharge pipe T_D Solenoid Valve 4Way V_4W Thermistor Suction pipe T_S Thermistor Ambient T_A Thermistor Cond Out T_CO Electronic Expansion Valve Main E_M Check Valve EEV Bypass CV_EB Heat...

Page 40: ... 2 OFM2 Thermistor Ambient T_A Thermistor Cond Out T_CO Heat Exchanger Main HX_M Thermistor Suction pipe T_S Check Valve EEV Bypass CV_EB Electronic Expansion Valve Main E_M IPM Cooler IPMC Heat Exchanger Intercooler HX_IC Thermistor EVI In T_EI Thermistor Liquid pipe T_L Electronic Expansion Valve EVI E_EVI Thermistor EVI Out T_EO Solenoid Valve EVI Bypass V_EB Ball Valve Liquid pipe BV_L Solenoi...

Page 41: ...rcuit powerSsc is greaterthan orequal to Ssc 2 at the interface point between the user s supply and the public system It is the responsibility of the installeroruserof the equipment to ensure by consultation with the distribution network operatorif necessary that the equipment is connected onlyto a supplywith a short circuit powerSsc greaterthan orequal to Ssc 2 Ssc 2 NOTE Model Ssc MVA AM080JXVHG...

Page 42: ...lation ambient temperature 30 C single multi conductor cables If the condition is different from the ones stated please consult an electrical installation expert and re select the power cable If the length of power cable exceed 50m re select the power cable considering the voltage drop Use a power cable made out of incombustible material for the insulator inner cover and the sheath outer cover Do ...

Page 43: ...ont part Install the power and communication cable using separate cable protection tube Fix a protection tube to the knock out hole on the outdoor unit by using a CD connector or bushing Make sure to use insulating bushing Main unit Sub unit Sub unit Ground cable Ground cable Ground cable Communication cable Power ground cable Power cable Power cable Power cable Communication cable between outdoor...

Page 44: ...e conditions Flexible PVC conduit PVC When the protection tube is installed indoor and not exposed to outside because it is embedded in concrete structure Class 1 flexible conduit Galvanized steel sheet When the protection tube is installed indoor but exposed to outside so there are risk of damage to the protection tube Class 1 PVC coated flexible conduit Galvanized steel sheet and Soft PVC compou...

Page 45: ...n of communication f f Maximum number of units that can be connected to the outdoor main unit is 64 so do not exceed this limit f f Communication cable should be connected in series as in the figure below and malfunction of communication can be occur if many units are connected to the same terminal f f Communication cable between indoor and outdoor units and communication cable between outdoor uni...

Page 46: ...pace f f If the installation space is narrow installer or otherworker may get injured during work and may also cause problem to the product f f If you install multiple number of outdoor units in one space make sure to secure enough ventilation space if there s any walls around the product that may disturb the air flow If enough ventilation space is not secured product may malfunction f f You may i...

Page 47: ...erthan 500mm Height of the wall on the side is not limited If the height of the wall exceeds by certain value h1 h2 additional clearance h1 2 h2 2 Half of the exceeded distance should be added to the service space S1 S2 1500 h1 500 h2 Front side Unit mm S1 h1 2 S2 h2 2 At Machinery Room Make sure to install both discharge duct and suction grille louver Static pressure of the discharge duct should ...

Page 48: ...und the outdoor unit to prevent the defrost water from the outdoor unit from stagnating overflowing or freezing near the installation space f f When the outdoor unit is installed on the roof check the strength and waterproof status of the roof Unit mm 960 760 100 80 80 80 6 0 100 X X Direction of the drainage Slope1 50 Drainage work forsingle installation B A 50 100 150 100 X X SECTION 80 80 80 80...

Page 49: ... outdoor unit on the rooftop check the strength and make sure to waterproof the rooftop f f Construct draining pit around the base construction and pay attention to the drainage around the outdoor unit Condensation or defrost water may form during outdoor unit operation f f If there s any possibility of small animals from entering the pipe outlet block the outlet as shown in the illustration Liqui...

Page 50: ...of snowfall install a snow prevention duct as a sufficient countermeasure to prevent snow from accumulating on the outdoor unit When the snow prevention duct is not installed frost may accumulate on the heat exchanger and heating operation may not work normally f f Air outlet of the duct should not be directed to the enclosed space Cautions regarding on installing the frame and selecting the base ...

Page 51: ... fall and cause personal injury When installing on a rooftop subject to strong wind countermeasures must be taken to prevent the unit from falling down Use a frame that is resistant to corrosion CAUTION 180 AM140 160 180 200 220 XV 560 22 05 1295 50 98 560 22 05 2400 94 49 1732 68 19 1255 49 41 1080 42 52 1192 46 93 552 21 73 2415 95 08 406 15 98 640 25 20 1252 49 29 1315 51 77 550 21 65 871 34 29...

Page 52: ...ible Flaring tool Pipe flaring Refrigerant machine oil Apply refrigerant oil on flared part Exclusive etheroil esteroil alkali benzene oil orsynthetic oil Torque wrench Connect flare nut with pipe Compatible Pipe bender Pipe bending Nitrogen gas Airtightness test Prevent oxidation within the pipe Welder Pipe welding Manifold gage Airtightness test additional refrigerant charging Vacuuming charging...

Page 53: ... the pipe main pipe by one grade which connects between the outdoor unit to the first branch joint f f For H R model When the pipe length including elbow between an outdoor unit and the farthest indoor unit exceeds 90m you must increase the size of the liquid pipe by one grade among the pipes main pipe which connects between the outdoor unit to the first branch joint H P 33 6 kW 40 0 kW D E C A B ...

Page 54: ...kW Ø 12 70 Ø 28 58 Ø 15 88 Ø 28 58 33 7 kW 40 0 kW 40 1 kW 45 0 kW Ø 31 75note2 45 1 kW 50 4 kW Ø 15 88 Ø 19 05 50 5 kW 56 0 kW 56 1 kW 63 3 kW 63 4 kW 70 3 kW Ø 34 92 Ø 38 10note3 70 4 kW 98 4 kW Ø 19 05 Ø 22 22 98 5 kW 135 2 kW Ø 41 28 Ø 41 28 135 3 kW 169 0 kW Ø 53 98 169 1 kW 252 0 kW Ø 22 22 Ø 53 98 Ø 25 40note1 Maximum pipe length The pipe length between an outdoorunit and the farthest indoo...

Page 55: ...22 Ø 25 40 note1 28 2 kW 40 0 kW Ø 12 70 Ø 28 58 Ø 15 88 Ø 28 58 40 1 kW 45 0 kW Ø 31 75 note2 45 1 kW 63 3 kW Ø 15 88 Ø 19 05 63 4 kW 70 3 kW Ø 34 92 Ø 38 10 note3 70 4 kW 98 4 kW Ø 19 05 Ø 22 22 98 5 kW 135 2 kW Ø 41 28 Ø 41 28 135 3 kW 169 0 kW Ø 53 98 Over169 0 kW Ø 22 22 Ø 53 98 Ø 25 40 note1 Note1 If Ø 25 40 pipe is not available on site use Ø 28 58 pipe Note2 If Ø 31 75 pipe is not availabl...

Page 56: ...oroutdoorunit C MXJ TA3419M 135 2 kW and below MXJ TA4122M Over135 2 kW f f First branch joint D Make a selection according to outdoor unit capacity Classification Outdoorunit capacity kW Model name of the branch joint Y joint D 40 0 kW and below MXJ YA2512M 40 1 kW 45 0 kW MXJ YA2812M 45 1 kW 67 2 kW MXJ YA2815M 67 3 kW 95 2 kW MXJ YA3419M 95 3 kW 135 2 kW MXJ YA4119M Over135 2 kW MXJ YA4422M ...

Page 57: ...nit D apply the pipe size D 1 Y joint Classification Model name Specification kW Y joint E MXJ YA1509M 15 0 kW and below MXJ YA2512M 15 1 kW 40 0 kW MXJ YA2812M 40 1 kW 45 0 kW MXJ YA2815M 45 1 kW 70 3 kW MXJ YA3419M 70 4 kW 98 4 kW MXJ YA4119M 98 5 kW 135 2 kW MXJ YA4422M Over135 2 kW 2 Distribution header Classification Model name Specification kW Distribution header E MXJ HA2512M 45 0 kW and be...

Page 58: ...70 Ø 19 05 Ø 15 88 22 5 kW 28 1 kW Ø 22 22 Ø 19 05 Ø 22 22 Ø 19 05 28 2 kW 33 6 kW Ø 12 70 Ø 28 58 Ø 15 88 Ø 28 58 33 7 kW 40 0 kW Ø 22 22 Ø 22 22 40 1 kW 45 0 kW 45 1 kW 50 4 kW Ø 15 88 Ø 19 05 50 5 kW 56 0 kW Ø 28 58 Ø 28 58 56 1 kW 63 3 kW 63 4 kW 70 3 kW Ø 34 92 Ø 34 92 70 4 kW 98 4 kW Ø 19 05 Ø 22 22 98 5 kW 135 2 kW Ø 41 28 Ø 34 92 Ø 41 28 Ø 34 92 135 3 kW 169 0 kW 169 1 kW 252 0 kW Ø 22 22 ...

Page 59: ...gas pipe 15 0 kW and below Ø 9 52 Ø 15 88 Ø 15 88 15 1 kW 22 4 kW Ø 19 05 22 5 kW 28 1 kW Ø 22 22 Ø 19 05 28 2 kW 33 6 kW Ø 12 70 Ø 28 58 33 7 kW 45 0 kW Ø 22 22 45 1 kW 50 4 kW Ø 15 88 50 5 kW 63 3 kW Ø 28 58 63 4 kW 70 3 kW Ø 34 92 70 4 kW 98 4 kW Ø 19 05 98 5 kW 135 2 kW Ø 41 28 Ø 34 92 135 3 kW 169 0 kW Over169 0 kW Ø 22 22 Ø 53 98 Ø 41 28 Size of the pipe between the branch joint and the indo...

Page 60: ...3419M 95 3 kW 135 2 kW MXJ YA4119M Over135 2 kW MXJ YA4422M High pressure Y joint D 22 4 kW MXJ YA1500M 22 5 kW 67 2 kW MXJ YA2500M 67 3 kW 135 2 kW MXJ YA3100M Over135 2 kW MXJ YA3800M f f Branch joint E Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch However if the size of the pipe between branch joints E is bigger than the size of the ...

Page 61: ...52 10 m Ø9 52 10 m Ø9 52 10 m Ø6 35 5 m Ø9 52 10 m 46 4 kW 4 5 kW 5 6 kW 5 6 kW 7 1 kW 7 1 kW 7 1 kW 7 1 kW 3 6 kW Ø9 52 1m Ø12 70 5 m Ø15 88 10 m Ø 1 2 70 10 m Ø9 52 15 m Ø9 52 10 m Ø12 70 10 m Ø9 52 18 m Ø9 52 18 m Ø9 52 25 m Ø9 52 15 m Ø9 52 10 m MCU MCU Ø6 35 2 m 2 8 kW 7 1 kW 11 2 kW 7 1 kW 11 2 kW 7 1 kW 7 1 kW 7 1 kW Ø6 35 15 m 61 6 kW 33 6 kW 28 0 kW ...

Page 62: ...ET AM280KXVAGH ET AM300KXVAGH ET Basicamount 8 4 8 4 14 0 14 0 14 0 14 0 Classification AM100MXVDGH ET AM120MXVDGH ET AM140MXVDGH ET AM160MXVDGH ET AM180MXVDGH ET Basicamount 5 5 6 5 7 7 8 4 8 4 Classification AM080JXVHGR EU AM100JXVHGR EU AM120JXVHGR EU AM140JXVHGR ET AM160JXVHGR ET AM180JXVHGR ET Basicamount 6 5 6 5 6 5 9 4 9 4 8 4 Classification AM200JXVHGR ET AM220JXVHGR ET AM240MXVGNR ET AM26...

Page 63: ... NMDE 0 24 0 24 0 24 0 28 0 28 0 28 0 32 0 54 0 68 0 68 0 91 MSPduct withdrainpump AM KNMDE 0 24 0 24 0 24 0 28 0 28 0 28 0 32 0 54 0 68 0 68 0 91 HomeDuct AM KNLDEH 0 13 0 13 0 13 0 17 Ceiling AM FNCDE AM JNCDK 0 39 0 39 0 56 0 95 Console AM NJDE 0 16 0 27 0 27 0 27 0 27 Neoforte AM FNTDE 0 24 0 24 0 24 0 24 0 36 0 36 Neoforte withEEV AM FNQDE 0 34 0 34 0 34 0 34 0 51 0 51 0 51 AR5000 AM JNADK 0 ...

Page 64: ...ation Size of liquid pipe Length m Unit amount of refrigerant kg m Amount of additional refrigerant kg Total amount of additional refrigerant kg Liquid pipe ⓐ Ø 6 35 35 0 02 0 7 ⓐ 5 575 Ø 9 52 50 0 06 3 0 Ø 12 70 15 0 125 1 875 Classification Model name of indoor unit Number of units Unit amount of refrigerant kg EA Amount of additional refrigerant kg Total amount of additional refrigerant kg Indo...

Page 65: ...efrigerant ⓐ ⓑ 11 965 4 66 16 625 kg Tempergrade and minimum thickness of the refrigerant pipe Outerdiameter mm Minimum thickness mm Tempergrade Ø 6 35 0 70 Annealed Ø 9 52 0 70 Ø12 70 0 80 Ø15 88 1 00 Ø19 05 0 90 Drawn Ø 22 22 0 90 Ø 25 40 1 00 Ø 28 58 1 10 Ø 31 75 1 10 Ø 34 92 1 21 Ø 38 10 1 35 Ø 41 28 1 43 Ø 44 45 1 60 Ø 50 80 2 00 Ø 53 98 2 10 For pipes larger than Ø 19 05 drawn type C1220T 1 ...

Page 66: ...n order among outdoor units f f Height of the connection pipe should be same or lower than the ones connected to the outdoor units f f Check the changes in comparison with the DVM II III and IV Caution Correct installation Incorrect installation Refrigerant pipes should be connected at the same orlowerlevel than the ones connected to the outdoorunit Refrigerant pipes must be connected by the side ...

Page 67: ...joint MCU MCU MCU MCU MCU MCU Note1 Note1 Direct connected indoorunit without MCU forHR only This indoorunit can only be used forcooling operation Heating operation is not possible Connect indoorunit to liquid and low pressure gas pipe Change the installation option fordirect connected indoorunit without MCU referto the indoorunit installation manual ...

Page 68: ...stalling onlywith Y joint Branch joint Outdoorunit Indoorunit Branch joint Outdoorunit Indoorunit Installing with Y joint and distribution header Branch joint Distribution header Outdoorunit Indoorunit Outdoorunit Indoorunit Distribution header Branch joint Installing onlywith distribution header Outdoorunit Indoorunit Distribution header Outdoorunit Indoorunit Distribution header ...

Page 69: ...nt and distribution header a b c d e f g h i j k 1000m Installing onlywith distribution header a b c d e f g h i 1000m Outdoorunit Outdoor unit Module installation Pipelength 10 m or less x 10 m y 10 m z 10 m Equivalent length 13 m or less x 13 m y 13 m z 13 m Maximum allowable height difference of pipe Outdoorunit Indoorunit 110 110m Note 2 H1 110 110m Indoorunit Indoorunit 50m orless H2 50m But ...

Page 70: ...branch joint and the outdoorunit is not increased by1 grade a b c d e f g 2 h i j k l m n p 1000 m If the size of pipe main pipe between the first branch joint and the outdoorunit is increased by 1 grade a b c d e f g 2 h i j k l m n p 1000 m Each Y joint Each indoorunit h i j p 45 m Difference between the distance of the outdoorunit to the farthest indoorunit and nearest indoorunit 45m a b c d e ...

Page 71: ...200 m or less 220 m or less Installing only with MCU a g j 200 m 220 m Equivalent length Y joint 0 5 m Distribution header 1 m MCU 1 m Installing with MCU and Y joint a b h k 200 m 220 m Total length of pipe 1000 m or less Installing only with MCU a b c d e f g h i j 1000 m Installing with MCU and Y joint a b c r 1000 m Outdoor unit Indoor unit Pipe length 10 m or less x 10 m y 10 m z 10 m Equival...

Page 72: ... 30 m Maximum allowable length after branch joint First branch joint Farthest Indoor unit Pipe length 45 m or less Installing only with MCU g j 45 m Installing with MCU and Y joint b h k 45 m l m q 45 m l r 45 m 45 90 m Note 2 Required conditions must be satisfied EEV kit Model name Remarks EEV kit Indoorunit Actual pipe length 2 m MEV E24SA 1 indooor Apply to products without EEV Wall mount ceili...

Page 73: ...t increased by1 grade a b l m x 2 c d e f g h i j k n o p q r 1000 m If the size of pipe main pipe between the first branch joint and the outdoor unit is increased by1 grade a b l m x 2 c d e f g h i j k n o p q r 1000 m MCU Each indoor unit c d c e c f g h i h j h k n o p q r 45 m Difference between the distance of the outdoor unit to the farthest indoor unit and nearest indoor unit 45 a b h k a ...

Page 74: ...8 units Up to 8 units Up to 8 units Up to 8 units The maximum capacity of the connectable indoor units at one port 16 kW 16 kW 16 kW 16 kW The maximum capacity of the connectable indoor units 61 6 kW 61 6 kW 32 0 kW 16 kW Internal EEV Not included Indoorunits without internal EEV AM NTDE AM NADE can not be connected directly to the MCU Please connect these indoorunits using EEV kit MEV E SA MXD E ...

Page 75: ... only and use Y connector on 5 0 16 kW indoor unit In case of using Y connector it is onlyconnectable forport combination at below Connectable port combination forY connector A B port C D port E F port Non connectable port combination forY connector B C port D E port non continuous port Set Dip Switch option for using Y connector 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 S WOption S WOption S WO...

Page 76: ... gas pipe conection welding High pressure gas pipe connection welding Liquid pipe connection welding When installing MCU use the pattern sheet for installation that is provided with the product When welding the gas pipes protect the product with the flame proof sheet When connecting the MCU with outdoor units default direction is set in the MCU If installing opposite direction weld the enclosed co...

Page 77: ...C Wired Remote Controller Simple Type MWR SH00N DVM CAC Wired Remote Controller Touch Simple Type MWR SH10N DVM CAC ERVWired Remote Controller MWR VH12N ERV Olny DVM CAC Wired Remote Controller MWR WW00N EHS Only EHS ReceiverKIT MRK A10N DVM CAC Zone Controller MWR ZS00N Mastercontroller Dampercontroller DVM CAC Zone Controller MWR ZS10N Slave controller DVM CAC Zone Controller MRW TS External roo...

Page 78: ...nterface Module MIM N01 DVM CAC ERV Interface Module MIM N10 DVM CAC Integrated management System DMS2 5 MIM D01AN DVM CAC S NET3 MST P3P DVM CAC Gate Way BACnet Gateway MIM B17BN DVM CAC Lonworks Gateway MIM B18BN DVM CAC External Contact Interface Module MIM B14 DVM CAC MTFC Multi Tenant Function Controller MCM C210N DVM SIM Signal Interface Module MIM B12N DVM CAC PIM Pulse Interface Module MIM...

Page 79: ... DVM CAC Others External Room Sensor MRW TA DVM CAC Operation Mode Selection Switch MCM C200 DVM Module Controller MCM A00N CHILLER Only CHILLER FCU Interface Module MIM F10N CHILLER Only CHILLER NOTE In case you want more information about the accessories please refer to the control and accessories TDB on pvi Samsung com site ...

Page 80: ...oller MCM A300N DVM CAC WIFI KIT MIM H03N MIM H03 DVM CAC Interface Module MIM N01 MIM N01 DVM CAC ERV Interface Module MIM N10 MIM N10 DVM CAC Integrated management System DMS2 5 MIM D01AN MIM D00A DVM CAC S NET3 MST P3P MST P3P DVM CAC GateWay BACnet Gateway MIM B17BN MIM B17 DVM CAC Lonworks Gateway MIM B18BN MIM B18 DVM CAC External Contact Interface Module MIM B14 MIM B14 DVM CAC MTFC Multi T...

Page 81: ... Y Joint Only H R OutdoorUnit MXJ TA3100M 135 2 kW and below MXJ TA3800M 140 2 kW and Over Distribution Header MXJ HA2512M 45 0 kW and below for4 rooms MXJ HA3115M 70 3 kW and below for8 rooms MXJ HA3819M Over70 3 kW 135 2 kW and below for8 rooms MCU MCU S6NEK2N 6 ports max 61 6kW 16kW 1port MCU S4NEK3N 4 ports max 61 6kW 16kW 1port MCU S2NEK2N 2 ports max 32 0kW 16kW 1port MCU S1NEK1N 1 port max1...

Page 82: ...PC4SUSMEN 4Way Cassette S 600x600 Classic PC4NUSKAN 4way Cassette S Waffle PC4NUSKEN 4way Cassette S Classic PC4NBSKAN 4way Cassette S Waffle Black PC4NUDMAN 360 CST Square White PC4NUNMAN 360 CST Circular White PC4NBDMAN 360 CST Square Black PC4NBNMAN 360 CST Circular Black S Plasma lon KIT MSD CAN1 Option 1Way 4Way 4Way 600x600 360 Big Ceiling Include Console MSD EAN1 Option Duct S Big Duct ERV ...

Page 83: ...DP M075SGU3D MSP S Duct 5 6 7 1 kW MDP E075SEE3D Slim Duct 2 0 14 0 kW MDP G075SP Duct S External All Capacities BIG Duct MDP G075SQ Duct S Internal 3 5 kW 14 kW BIG Duct AHU KIT MXD K025AN 7 0 kW 8 75 kW MXD K050AN 14 0 kW 17 5 kW MXD K075AN 21 0 kW 26 25 kW MXD K100AN 28 0 kW 35 0 kW MXD A64K100E MCM D201N 28kW 35kW 56kW 70kW 84kW 105kW 112kW 140kW MDX A64K100E X 1 EA MDX A64K100E X 2 EA MDX A64...

Page 84: ...DP M075SGU3D O MDP E075SEE3D O MDP G075SP External All Capacities O O MDP G075SQ Internal O O S Plasma Ion KIT MSD CAN1 O O MSD EAN1 O Motion detect Sensor MCR SMA O ERVCO2 Sensor MOS C1 O EEVKITS MEV E SA 1 Indoor O MXD E K A 2 3 Indoor O MCU KIT MCU S6NEK2N 6 ports max61 6kW O O O O O O O O O O O O O O O O O O O O O O O MCU S4NEK3N 4 ports max61 6kW O O O O O O O O O O O O O O O O O O O O O O O ...

Page 85: ... PM SE Head Office Suwon Korea 129 Samsung Ro Yeongtong Gu Suwon City Gyeonggi Do Korea 16677 Website www samsung com http btsp samsunggsbn com Email airconditioner samsung com Images and data in this book may subject to change without prior notice ...

Reviews: