Product Specifications
2-62
Samsung Electronics
Outdoor Unit
(cont.)
Type
DVM S
Model
AM240KXVGGH/ET
AM260KXVGGH/ET
Power Supply (Outdoor Unit) [Φ, #, V, Hz]
3,4,380-415,50
3,4,380-415,50
System
Mode
HEAT PUMP
HEAT PUMP
Performance (nominal)
24 HP
26 HP
Capacity
Cooling [kW]
67.2 kW
72.8 kW
Cooling [Btu/h]
229,300 Btu/h
248,400 Btu/h
Heating [kW]
67.2 kW
72.8 kW
Heating [Btu/h]
229,300 Btu/h
248,400 Btu/h
Power Input
(Rated)
Cooling 1)
18.61 kW
20.92 kW
Heating 2)
13.20 kW
15.17 kW
Current Input
(Rated)
Cooling 1)
29.80 A
33.60 A
Heating 2)
21.20 A
24.30 A
Power
MCA [A]
55.0 A
60.0 A
MFA [A]
63.0 A
75.0 A
Energy Efficiency EER (Rated Cooling)
3.61
3.48
COP (Rated Heating)
5.09
4.80
Compressor
Type
Scroll Inverter
Scroll Inverter
Output(kW)
6.76 x 2 kW
7.81 x 2 kW
Model
DS-GB070FAVA x 2
DS4GJ5080FVA x 2
Oil (Type)
PVE
PVE
Oil (Initial Charge) [cc]
1100 x 2 cc
1400 x 2 cc
Fan
Type
Propeller
Propeller
Motor (Output) [W]
620 x 2 W
620 x 2 W
Air Flow Rate (High / Mid / Low) [CMM]
340 CMM
340 CMM
Air Flow Rate(High/Mid/Low)[L/S]
-
-
External Static Pressure (Min / Std / Max)
[mmAq]
8.0 mmAq
8.0 mmAq
External Static Pressure (Min / Std / Max)
[Pa]
- Pa
- Pa
Piping Connec-
tions
Liquid Pipe (Φ, mm)
15.88 mm
19.05 mm
Liquid Pipe (Φ, inch)
5/8"
3/4"
Gas Pipe (Φ, mm)
34.92 mm
34.92 mm
Gas Pipe (Φ, inch)
1+3/8"
1+3/8"
Installation Max. Length [m]
200(220) m
200(220) m
Installation Max. Height [m]
50(110)/40(110) m
50(110)/40(110) m
Field Wiring
Power Source Wire
-
-
Transmission Cable
-
-
Refrigerant
Type
R410A(Fluorinated green-
house gas, GWP=2,088)
R410A(Fluorinated green-
house gas, GWP=2,088)
Factory Charging (kg)
14.0 kg
14.0 kg
Factory Charging (tCO2e)
29.23 tCO2e
29.23 tCO2e
Sound
Sound Pressure
69 dBA
69 dBA
Sound Power
90 dBA
90 dBA
External Dimen-
sion
(Outdoor Unit)
Net Weight(kg)
342.0 kg
350.0 kg
Shipping Weight (kg)
364.0 kg
372.0 kg
Net Dimensions (WxHxD) (mm)
1295x1795x765 mm
1295x1795x765 mm
Shipping Dimensions (WxHxD) (mm)
1363x1987x832 mm
1363x1987x832 mm
Operating Temp.
Range
Cooling (
℃
)
-5 ~ 48
℃
-5 ~ 48
℃
Heating (
℃
)
-25 ~ 24
℃
-25 ~ 24
℃
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.
Summary of Contents for AM080*XV Series
Page 205: ...Samsung Electronics 5 1 5 PCB Diagram and Parts List 5 1 ASS Y PCB MAIN...
Page 208: ...PCB Diagram and Parts List 5 4 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC...
Page 210: ...PCB Diagram and Parts List 5 6 Samsung Electronics ASS YPCBMAIN HUB cont DC...
Page 216: ...PCB Diagram and Parts List 5 12 Samsung Electronics 5 4 ASS YPCBFAN Model 1 FANchassis...
Page 218: ...PCB Diagram and Parts List 5 14 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis...
Page 241: ...Cycle Diagram 7 10 Samsung Electronics 7 16 AM240 260 280 300MXVAGC...