AM140/160/180/200/220/240/260/280/300KXV
6666
AM080/100/120/140/160/180/200/220/240/260/280/300MXVA
6
C
※
Setting
outdoor
insta
ll
option
Step
Button
Display
Description
Note
Start
Outdoor unit address
Quantity of indoor units
Main unit?
No
No
Yes
Yes
Save
Heat recovery?
Quantity of MCUs
Outdoor unit address
Step1
Outdoor unit
display
Setting required-
Step2
Press (K1+K2) for
2 seconds
Unit address
for module
combination
00: Main unit
K4 x 1 time
01: Sub1 unit
K4 x 2 times
02: Sub2 unit
K4 x 3 times
03: Sub3 unit
Step3
If it is main unit, go to step4.
Otherwise, press K2 button for 2 seconds to save & exit
(system will be reset)
Quantity of indoor units
Step4
Ready to set-
Step5
K2 x n times
Press K1
X
Tens digit (0 ~ 6)
Ex) 03: 3 units
64: 64 units
K4 x n times
X
Ones digit (0 ~ 9)
* K4: Press for 2 seconds - automatic detection of indoor units’ quantity
Step6
If it is heat recovery model, go to step 7.
Otherwise, press K2 button for 2 seconds to save & exit
(system will be reset)
Quantity of MCUs * Heat recovery model only
Step7Press K1
Ready to set-
Step8
K2 x n times
X
Tens digit (0 ~ 1)
Ex) 03: 3 units
16: 16 units
K4 x n times
K2: long
X
Ones digit (0 ~ 9)
* K4: Press for 2 seconds - automatic detection of MCUs' quantity
Step9
Save
Restart
* Press K1 for 2 seconds to exit without save regardless of setting step.
K1 K2 K3 K4
Summary of Contents for AM080*XV Series
Page 205: ...Samsung Electronics 5 1 5 PCB Diagram and Parts List 5 1 ASS Y PCB MAIN...
Page 208: ...PCB Diagram and Parts List 5 4 Samsung Electronics 5 2 ASS YPCBMAIN HUB AC...
Page 210: ...PCB Diagram and Parts List 5 6 Samsung Electronics ASS YPCBMAIN HUB cont DC...
Page 216: ...PCB Diagram and Parts List 5 12 Samsung Electronics 5 4 ASS YPCBFAN Model 1 FANchassis...
Page 218: ...PCB Diagram and Parts List 5 14 Samsung Electronics ASS YPCBFAN cont Model 2 FAN chassis...
Page 241: ...Cycle Diagram 7 10 Samsung Electronics 7 16 AM240 260 280 300MXVAGC...