Product Specifications
Samsung Electronics
17
غ
Premium Energy Efficiency Type (AM***KXWDCH*)
System Model
Capacity of Single Unit (Ton)
Capa(ton)
Code
No. of Modules
3
4
5
3
AM038KXWDCH*
1
1
4
AM048KXWDCH*
1
1
5
AM055KXWDCH*
1
1
ሪ
Make sure to use an indoor unit that is compatible with DVM S Water-GEO.
ሪ͑
Indoor units can be connected within the range indicated in following table.
ሪ͑
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of
the indoor unit may decrease.
ሪ
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × Σ( Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ( Outdoor unit capacity)
͑͑͑ఐ ͑
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64 since outdoor
unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the indoor unit address was assigned
from 64~79, E201 error will occur.
͑͑͑ఐ
Maximum 32 Wall-mount type indoor units with EEV (AM****NQDEH*, AM***JNV*) can be connected.
2-2 Model names of Indoor/Outdoor Unit
(cont.)
2-2-1 Outdoor unit combination
(cont.)
Summary of Contents for AM038KXWDCH
Page 168: ...Samsung Electronics 165 5 PBA Diagram and Parts List 5 1 ASS Y PBA MAIN Ŷ Push buttons Type ...
Page 170: ...PBA Diagram and Parts List Samsung Electronics 167 5 1 ASS Y PBA MAIN cont Ŷ DIP S W Type ...
Page 172: ...PBA Diagram and Parts List Samsung Electronics 169 5 2 ASS Y PBA MAIN HUB Ŷ AC ...
Page 174: ...PBA Diagram and Parts List Samsung Electronics 171 5 2 ASS Y PBA MAIN HUB cont Ŷ DC ...