4-3-16 MCU/MCU subcooler entrance/exit sensor error (Open/Short)
1. Cause of problem
Is the sensor connector connected
on the PBA ?
Is the resistor value matching with
“NOTE1” table?
Separate the connector from the PBA and
measure the resistance value
between the 2 terminals.
Restart operation after replace the PBA
Restart operation after
connecting the connector to PBA
Replace this part as it is
the defective itself.
No
No
Yes
Yes
Yes
NOTE1
Temperature(°C)
Resistance(KΩ)
70
60
50
40
30
20
10
0
-10
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Outdoor unit
display
(MCU subcooler)
(MCU)
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation
Defrost
Timer
Fan
Filter/MPI Operation
Defrost
Timer
Filter
Operation
Timer
Turbo
×
×
◑
◑
◑
×
◑
◑
◑
●
◑
◑
※ ●
: ON
◑
: Flash ×: OFF
Judgment
Method
- Detect according to temperature detected with the MCU / MCU subcooler entrance/exit pipe temperature thermistor.
Cause of
problem
- MCU / MCU subcooler pipe entrance/exit sensor is defective. (open/short)
4-3 Appropriate Measures for Different Symptom
(cont.)
Summary of Contents for AM038KXWDCH
Page 168: ...Samsung Electronics 165 5 PBA Diagram and Parts List 5 1 ASS Y PBA MAIN Ŷ Push buttons Type ...
Page 170: ...PBA Diagram and Parts List Samsung Electronics 167 5 1 ASS Y PBA MAIN cont Ŷ DIP S W Type ...
Page 172: ...PBA Diagram and Parts List Samsung Electronics 169 5 2 ASS Y PBA MAIN HUB Ŷ AC ...
Page 174: ...PBA Diagram and Parts List Samsung Electronics 171 5 2 ASS Y PBA MAIN HUB cont Ŷ DC ...