21
ENGLISH
Selecting installation location
Decide the installation location, with the consideration of the following conditions, under user’s approval.
f
Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in residential areas,
keep the operation hours in mind.)
f
Place where structure can bear the weight and vibration of the outdoor unit.
f
Place with flat surface where rainwater does not settle or leak.
f
Place where it is not exposed to strong wind.
f
Well ventilated place with sufficient service place for repairs and maintenance. (Discharge duct can be purchased
separately)
f
Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance.
f
Place where it allows easy waterproofing and draining work for the condensation water generated from the outdoor unit
during heating operation.
f
Place where there is no risk of inflammable gas leakage.
f
Place where there is no direct influence of snow or rain.
Installation Guide at the seashore
Make sure to follow below guides when installing at the seashore.
1. Do not install the product in a place where it is directly exposed to sea water and sea breeze.
- Make sure to install the product behind a structure (such as building) that can block see breeze.
- Even when it is inevitable to install the product in seashore, make sure that product is not directly exposed to sea
breeze by installing a protection wall.
2. Consider that the salinity particles clinging to the external panels should be sufficiently washed out.
3. Because the residual water at the bottom of the outdoor unit significantly promotes corrosion, make sure that the slope
does not disturb drainage.
- Keep the floor level so that rain does not accumulate.
- Be careful not to block the drain hole due to foreign substance
4. When product is installed in seashore, periodically clean it with water to remove attached salinity.
5. Make sure to install the product in a place that provides smooth water drainage.
Especially, ensure that the base part has good drainage.
6. If the product is damaged during the installation or maintenance, make sure to repair it.
7. Check the condition of the product periodically.
- Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG
(Code : MOK-220SA) or commercial water repellent grease and wax, etc., based on the product condition.
- When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate measures like
covering the product.
8. If the product is installed within 500 m of seashore, special anti corrosion treatment is recommended for the product.