10
Preparing for installation
Model name for combination
AM580JXVAFH1AZ
AM600JXVAFH1AZ
AM620JXVAFH1AZ
AM640JXVAFH1AZ
Number of individual outdoor units
3
3
4
4
Combined outdoor unit
AM080JXVAFH
AM100JXVAFH
1
AM120JXVAFH
1
2
AM140JXVAFH
AM160JXVAFH
AM180JXVAFH
1
AM200JXVAFH
2
3
2
2
Rated capacity
Cooling (kW)
162.4
168.0
173.6
179.2
Cooling (Btu/h)
554 200
573 300
592 300
611 400
Heating (kW)
182.7
189.0
195.3
201.6
Heating (Btu/h)
623 500
645 000
666 500
688 000
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
81.2
84.0
86.8
89.6
Minimum (Btu/h)
277 000
286 500
296 200
305 600
Maximum (kW)
211.1
218.4
225.7
233.0
Maximum (Btu/h)
720 400
745 200
770 000
794 800
Maximum number of connectable indoor
units
64
64
64
64
Model name for combination
AM660JXVAFH1AZ
AM680JXVAFH1AZ
AM700JXVAFH1AZ
AM720JXVAFH1AZ
Number of individual outdoor units
4
4
4
4
Combined outdoor unit
AM080JXVAFH
AM100JXVAFH
AM120JXVAFH
1
1
1
1
AM140JXVAFH
1
AM160JXVAFH
1
AM180JXVAFH
1
AM200JXVAFH
2
2
2
3
Rated capacity
Cooling (kW)
185.6
190.6
196.0
201.6
Cooling (Btu/h)
633 300
650 300
668 800
687 900
Heating (kW)
208.8
214.2
220.5
226.8
Heating (Btu/h)
712 500
731 000
752 500
774 000
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
92.8
95.3
98.0
100.8
Minimum (Btu/h)
316 500
325 100
334 300
343 800
Maximum (kW)
241.3
247.8
254.8
262.1
Maximum (Btu/h)
823 200
845 400
869 400
894 200
Maximum number of connectable indoor
units
64
64
64
64