Installation option (Detailed)
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Reserved
Use of external room temperature sensor /
Minimizing fan operation when thermostat is off
Use of central
control
Compensation of the
fan RPM
Indication
and
details
Indication Details Indication Details
Indication
Details
Indication Details Indication
Details
0
2
Use of External
room temperature
sensor
Minimizing fan
operation when
thermostat is off
0
Disuse
0
Disuse
(recessed
installation)
0
Default
Default
1
Use
Disuse
2
Disuse
Use (Heating)
3
Use
Use (Heating)
4
Disuse
Use (Cooling)
5
Use
Use (Cooling)
1
Use
1
RPM
compensation
6
Disuse
Use (Heating /
Cooling)
7
Use
Use (Heating /
Cooling)
8
Disuse
Use (Cooling Ultra
Low Fan )
9
Use
Use (Cooling Ultra
Low Fan )
A
Disuse
Use (Heating /
Cooling Ultra Low
Fan )
B
Use
Use (Heating /
Cooling Ultra Low
Fan )
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Function
Page
Use of drain pump
Use of Hot Coil
Use of heater
Controller variables for auxiliary heater
Reserved
Indication
and
details
Indication Details Indication Details Indication Details Indication Details
Indication
Details
1
0
Disuse
0
Disuse
0
Disuse
Set temperature for
auxiliary heat on
Time delay for
auxiliary heat on
0
No temperature
offset
No delay
1
No temperature
offset
10 minutes
2
No temperature
offset
20 minutes
1
Use
1
Use
1
Use
3
1.5°C
No delay
4
1.5°C
10 minutes
5
1.5°C
20 minutes
6
3°C
No delay
7
3°C
10 minutes
8
3°C
20 minutes
2
Use with
3 minute
delay
-
-
2
Use
(Heater
time
delay)
9
4.5°C
No delay
A
4.5°C
10 minutes
B
4.5°C
20 minutes
C
6°C
No delay
D
6°C
10 minutes
E
6°C
20 minutes