Indoor power supply
Power supply
Max/Min(V)
Indoor power cable
220 to 240V, 50 Hz
±10%
0.75 to 1.5 mm², 3 wires
Communication cable
0.75 to 1.5 mm², 2 wires
11
13
7.5
9.0
18
13.8
AC power: M4 screw
Communication: M3.5 screw
Tightening torque (kgf • cm)
M3.5
8.0 to 12.0
M4
12.0 to 18.0
• 1 N·m = 10 kgf·cm
• Power supply cords of parts of appliances for
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer
room or a server room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
Step 13 Optional: Extending the
power cable
1
Prepare the following tools.
Tools
Spec
Shape
Crimping pliers
MH-14
Connection sleeve
(mm)
20xØ6.5 (HxOD)
Insulation tape
Width 19 mm
Contraction tube
(mm)
70xØ8.0 (LxOD)
2
As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
•
Peel off 20 mm of cable shields from the pre-
installed tube.
CAUTION
•
For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
•
After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
•
If cable wires are connected without using
connecting sleeves, their contact area becomes
reduced, or corrosion develops on the outer surfaces
of the wires (copper wires) over a long time. This
may cause an increase of resistance (reduction of
passing current) and consequently may result in a
fire.
20
20
20
60
120
180
Power cable
20
20
20
60
120
180
Pre-installed
tube for the
power cable
(Unit: mm)