11
Ins
tallation Pr
oc
edur
e
English
CAUTION
• Comply with the length and height limits described in
the figure above.
• For the product that uses the R-32 refrigerant, Install
the indoor unit on the wall 2.2 m or higher from the
floor.
Step 3 Optional: Insulating the body
of the indoor unit
A
D
B
C
Thickness: more than 10mm
Indoor
Unit
AJ026TNLDEG
AJ035TNLDEG
AJ052TNMDEG
700 X 440 X 199
900 X 480 X 260
A
700 X 200
900 X 260
B
700 X 200
900 X 260
C
440 X 200
480 X 260
D
440 X 200
480 X 260
Front/
Back
Insulate the front and back side in proper size at
the same time when insulating the suction duct
and discharge duct.
(Unit: mm)
NOTE
• Insulate the end of the pipe and some curved area by
using separate insulator.
• Insulate the discharge and suction part at the same
time when you insulate connection duct.
Step 4 Installing the indoor unit
When deciding on the location of the air conditioner
with the owner, the following restrictions must be taken
into account
1
Place the pattern sheet on the ceiling at the spot where
you want to install the indoor unit.
NOTE
• Since the diagram is made of paper, it may shrink or
stretch slightly due to temperature or humidity. For
this reason, before drilling the holes maintain the
correct dimensions between the markings.
2
Insert bolt anchors. Use existing ceiling supports or
construct a suitable support as shown in figure.
3
Install the suspension bolts depending on the ceiling type.
CAUTION
• Ensure that the ceiling is strong enough to support the
weight of the indoor unit. Before hanging the unit, test
the strength of each attached suspension bolt.
Ceiling support
Hole in anchor
Hole in plug
Suspension bolt (M8) - field supply
Concrete
Insert