Installation Procedure
English
Instal
lation Pr
oc
edur
e
Specification for circuit breaker and power supply cord
• Power supply cord is not supplied with air conditioner.
• Select the power supply cord in accordance with relevant local and national regulations.
• Wire size must comply with the applicable local and national code.
• Specifications for local wiring power supply cord and branch wiring are in compliance with local cord.
The specification for cables
Model
Main Power Supply
Cable
Indoor Power Supply
Cable
Communication Cable
FUSE
MCCB
Type
GL
Specification
Type
Specification
Type
Specification
Type
AJ036BXJ4CH
3G, 4.0 mm²
(8Kcmil or
0.0062 inch²
or 10AWG),
H05RN-F grade
or more
A
3G, 1.5 mm²
(3Kcmil or
0.0023 inch²
or 14AWG),
H05RN-F grade
or more
B
2G, 0.75 mm²
(1.5Kcmil or
0.0012 inch²
or 18AWG),
H05RN-F grade
or more
C
30A Frame: 35A
Trip: 30A 30A
AJ020CXS3CH
AJ024CXS4CH
AJ030CXS4CH
AJ036CXS4CH
AJ048BXJ5CH
3G, 6.0 mm²
(12Kcmil or
0.0093 inch²
or 8AWG),
H05RN-F grade
or more
40A Frame: 50A
Trip: 40A 40A
• Connect the power cable to the auxiliary circuit breaker.
An all-pole disconnection from the power supply must be incorporated in the fixed wiring with a contact opening of
≥0.12 inch (3 mm).
Tightening power terminal
• Connect the cables to the terminal board using the compressed ring terminal.
• Use rated cables only.
• Connect the cables with driver and wrench that can apply the rated torque to the screws.
• Make sure that appropriate tightening torque is applied for cable connection. If the terminal is loose, arc heat may
occur and cause fire and if the terminal is connected too firmly, terminal may get damaged.
Screw
Tighten Torque [lbf·ft (kgf·cm)]
M4
0.87 ~1.30 (12.0 ~ 18.0)