E-
21
ENGLISH
X
Field-supplied electrical components such as power switch, circuit breakers, wires, terminal blocks,
etc must be properly chosen with compliance with national legislation or regulation.
X
Switch off the power supply before making any connections.
X
All field wiring and components must be installed by a licensed electrician.
X
Use a dedicated power supply.
X
All power connections must be protected from dew condensation by thermal insulation.
X
The system shall be earthed. Do not earth the unit to a utility pipe, surge absorber or telephone
earth. Incomplete earth may cause electrical problems.
Layout of PCB
THERMOSTAT1(L)/
THERMOSTAT2(H)
CN85(White)
BACKUP HEATER
CN71(Yellow)
BOILER
CN74(Black)
2-WAY-1
CN78(Black)
3-WAY
CN77(White)
SOLAR-PUMP
CN86(White)
DHW tank temp.
(Default, 15m)
CN 53 (Red)
External room
temp.
(Optional, 15m)
CN 55 (White)
Wired
remote
controller
COMM2
CN 32 (Red)
SMPS circuit
Micom
LED
Communication
Load control
Fuse
EEV
CN 62 (Blue)
Flow switch
CN 51 (Blue)
COMM1
CN 31 (Red)
AC-POWER
CN01(Blue)
Wiring work
LED & Buzzer
CN 01 (White)
CN 02
(White)
WATER-PUMP
CN75(Red)
BOOSTER
CN73(Yellow)
Download port
CN10 (black)
THERMOSTAT
AC-POWER
CN84(Blue)
Solar temp.
CN52(Black)
Temp. Sensor
CN 54 (White)
1-2 : Water outlet ( TW3 )
3-4 : PIPE OUT ( TR2 )
5-6 : PIPE IN ( TR1 )
7-8 : PHE outlet ( TW2 )
9-10 : Water inlet( TW1 )
EEPROM
2-WAY
CN76(Red)
Summary of Contents for AEN080YDEHA
Page 1: ......
Page 11: ...E 11 ENGLISH Dimensional drawing 131 7 78 5 103 7 104 0 125 0 490 22 0 39 2 850 0 510 0 314 6 ...
Page 22: ...E 22 Wiring diagram AEN160YDGHA Wiring work Continued ...
Page 23: ...E 23 ENGLISH Wiring diagram AEN160YDEHA AEN080YDEHA ...
Page 38: ...E 38 DHW tank Continued Accessories Leg 3 Anode bar 1 Conduit 1 ...
Page 48: ......