Refrigerant pipe work
For all guide lines, specifications regarding refrigerant pipe work between the indoor unit and the outdoor
unit, please follow the outdoor unit installation manual.
Gas pipe (O.D.)
Liquid pipe (O.D.)
Tightening Torque
Final Torque
Indoor unit
15.9mm(5/8 inch)
9.5mm(3/8 inch)
400kg∙cm
450kg∙cm
Outdoor unit 15.9mm(5/8 inch)
9.5mm(3/8 inch)
700 kg∙cm
750kg∙cm
When connecting the refrigerant pipes, always use 2 wrenches/spanners for tightening or loosening
nuts. If not, piping connections can be damaged.
WATER
OUTLET
WATER
INLET
Liquid
pipe
Gas
pipe
Pipe work