Power Cable Specifications
f
f
The power cable is not supplied with air conditioner .
- Select the power supply cable in accordance with relevant local and national regulations .
- Wire size must comply with the applicable local and national code .
- Specifications for local wiring power cord and branch wiring are in compliance with local cord .
Model
Power source
RLA (A)
FLA
MCA
MOP
FAN1 (A)
FAN2 (A)
AC024JXADCH
208~230V/60Hz
9 .00
0 .48
-
22
20
AC030JXADCH
15 .10
0 .48
-
21 .8
30
AC036JXADCH
17 .00
0 .48
0 .48
23 .5
35
AC042JXADCH
17 .00
0 .48
0 .48
23 .5
35
AC048JXADCH
17 .00
0 .48
0 .48
23 .5
35
1 . RLA is based on AHRI 210/240 colling standard condition [Indoor temp . : 26 .7 °C / 80 °F(DB) / 19 .46 °C /
67 °F(WB), Outdoor temp . : 35 °C / 95 °F(DB)]
2 . Voltage tolerance is ± 10 % .
3 . Maxium allowable voltage between phases is 2 % .
Symbols
• RLA : Rated Load Ampere
• FLA : Full Load Ampere
• MCA : Minumum Circuit Ampere (A)
• MOP : Maximum Overcurrent Protective Device (A)
NOTE
Tightening power terminal
f
f
Connect the cables to the terminal board using the compressed ring terminal .
f
f
Use rated cables only .
f
f
Connect the cables with driver and wrench that can apply the rated torque to the screws .
f
f
Make sure that appropriate tightening torque is applied for cable connection . If the terminal is loose, arc heat may occur
and cause fire and if the terminal is connected too firmly, terminal may get damaged .
Tightening torque
M4
10 .4~13 .0 lbf•in
1 .2~1 .8 N•m
Communication : F1, F2
M5
17 .4~26 .0 lbf•in
2 .0~3 .0 N•m
1 phase AC power : L1, L2
Connecting the cable
14
4way Outdoor_북미향_IM_EN_DB68-05152A-00_CS6.indd 14
2015-01-05 오후 4:59:59