Troubleshooting
The table below give indication about self diagnostic routine . Some of error code requires activities exclusively for Authorized
Service Center .
Outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
Priority
Error number
Explanation
1
E471
Outdoor unit EEPROM Read/Write error (H/W)
2
E470
Outdoor unit EEPROM Read/Write error (Option)
3
E202
Communication error between indoor unit and outdoor unit (When there is no response from indoor
units after tracking is completed)
4
E201
Communication error between indoor unit and outdoor unit (Pre tracking failure or when actual
number of indoor units are different from the indoor unit quantity setting on the outdoor unit) Error
due to communication tracking failure after initial power supply (The error occurs with the failure
regardless of the number of devices)
5
E203
Communication error between outdoor unit inv - main micom
(For PF #4~#6 controller, error will be determined from the time when compressor turns on)
6
E221
Error on outdoor temperature sensor (Short or Open)
7
E108
Error due to repeated communication address
8
E251
Error on discharge temperature sensor of compressor 1 (Short or Open)
9
E231
Error on outdoor COND OUT sensor (Short or Open)
10
E320
Error on OLP sensor (Short or Open)
11
E485
Error on input current sensor of inverter 1 (Short or Open)
12
E474
Error on IPM Heat Sink sensor of inverter 1 (Short or Open)
13
E425
Reverse phase or open phase
14
E422
Blockage detected on high pressure pipe
15
E554
Gas leak detected
16
E416
System stop due to discharge temperature
17
E463
System stop due to OLP temperature control
18
E458
Fan speed error
19
E462
System stop due to full current control
20
E404
System stop due to overload protection control
21
E590
Inverter EEPROM CheckSum error
22
E464
System stop due to DC Peak
23
E473
Comp Lock error
24
E465
Compressor overload prevention
25
E468
Error on current sensor (Short or Open)
26
E461
Error due to operation failure of inverter compressor
27
E467
Error due to abnormal rotation of the compressor or unconnected wire of compressor
28
E469
Error on DC-Link voltage sensor (Short or Open)
29
E472
AC Line Zero Cross Signal out
OTHERS
32