![Samsung AC026MNLDKH Installation Manual Download Page 24](http://html.mh-extra.com/html/samsung/ac026mnldkh/ac026mnldkh_installation-manual_336721024.webp)
24
Installation Procedure
Ins
tallation Pr
oc
edur
e
English
Step 15 Optional: Extending the
power cable
1
Prepare a crimping tool and the following tools.
Tools
Spec
Shape
Crimping pliers
MH-14
Connection sleeve
(mm)
20xØ6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70xØ8.0
(LxOD)
2
As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
•
Peel off 20 mm of the wire shields of the tube.
CAUTION
•
For information about the power cable specifications for
indoor and outdoor units, refer to the installation manual.
•
After peeling off the tube wire, you must insert a
contraction tube.
Power cable
Pre-installed tube for the power cable
(Unit: mm)
(Unit: mm)
20
20
20
20
60
120
180
3
Insert both sides of core wire of the power cable into the
connection sleeve.
•
Method 1
: Push the core wire into the sleeve from
both sides.
•
Method 2
: Twist the wire cores together and push it
into the sleeve.
Method 1
Connection sleeve
Connection sleeve
Method 2
4
Using a crimping tool, compress the two points and flip it
over and compress another two points in the same location.
•
The compression dimension should be 8.0.
Compression
dimension
•
After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
5 mm
5 mm
Method 1
Method 2
Compress it 4 times.
Compress it 4 times.
5
Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
A total of three or more layers of insulation is required.
40 mm
35 mm
Method 1
Method 2
Insulation tape
Insulation tape
6
Apply heat to the contraction tube to contract it.
Contraction tube