8
Indoor unit installation
Ceiling support
Pad stopper
Bracket
Ceiling
17mm
20mm
Indoor unit
Gauge of
Dimensions
Concrete
Suspension bolt(M8)-field supply
Hole in anchor
Hole in plug
Insert
When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account.
1. Determine the position of the pipe and drain hose hole as seen in the
picture and drill the hole with an inner diameter of 65mm so that it slants
slightly downwards.
2. Insert bolt anchors, use existing ceiling supports or construct a suitable
support as shown in figure.
3. Install the suspension bolts depending on the ceiling type.
4. Screw eight nuts to the suspension bolts making space for hanging the
indoor unit.
5. Hang the indoor unit to the suspension bolts between two nuts.
6. Screw the nuts to suspend the unit. Cut a pad stopper and place it on the
bracket at this time.
7. Adjust the unit to the appropriate position considering the installation area
for the front panel.
1) Place the pattern sheet on the indoor unit.
2) Adjust a space between the ceiling and the indoor unit by using the gauge
of dimensions.
3) Fix the indoor unit securely after adjusting level of the unit by using a
leveler.
4) Remove the pattern sheet, connect the other cables and install the front
panel.
• Since the diagram is made of paper, it may shrink or stretch slightly
due to temperature or humidity. For this reason, before drilling the
holes maintain the correct dimensions between the markings.
• Piping must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed, lay the
piping into position for connection to the unit before placing the unit
inside the ceiling.
• Ensure that the ceiling is strong enough to support the weight of the
indoor unit. Before hanging the unit,
test the strength of each attached suspension bolt.
• If the length of suspension bolt is more than 1.5m, it is required to
prevent vibration.
• You must install all the suspension rods.
• It is important to leave sufficient space in the false ceiling to allow
access for maintenance or repairs to the drainage pipe connection,
the refrigerant pipe connection, or to remove the unit if necessary.