Drainpipe and drain hose installation

1  Push the supplied drain hose as far as possible over the drain socket.
2  Tighten the metal clamp as shown in the picture.
3  Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps.
4  Insulate the complete drain piping inside the building (field supply).  

If the drain hose cannot be sufficiently set on a slope, fit the hose with drain raising piping (field supply).

5  Push the drain hose up to insulation when connecting the drain hose to drain socket.

A-A’

Drain socket

Drain piping

Drain hose

Metal clamp

Large sealing pad

Tighten the clamp to the maximum 

until you can see eight holes. 

  When installing insulation in places and conditions below, use the same insulation that is used for high 

humidity conditions.

 

<Geological condition>

 

-  High humidity places such as shoreline, hot spring, near lake or river, and ridge (when the part of the 

building is covered by earth and sand.)

 

<Operation purpose condition>

 

- Restaurant ceiling, sauna, swimming pool etc.

 

<Building construction condition>

 

-  The ceiling frequently exposed to moisture and cooling is not covered.

 

 e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes 

frequently.

 

- The place where the pipe is installed is highly humid due to the lack of ventilation system.

Performing leak test & insulation

CAC CASSETTE TYPE 유럽-터키향_IM_32787A-14_EN.indd   12

2016-05-26   오후 5:18:52

Summary of Contents for AC***FB4DEH

Page 1: ...ype Series AC FB4DEH AC FB4PEH AC FB4FEH NS 4PXEA NS 4DXEA NS 4ZXEA Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product DB98 32787A 15 IT FR ES EN PT EL DE ...

Page 2: ...ortheapplicationsforwhichithasbeendesigned theindoorunitisnotsuitabletobe installedinareasusedforlaundry Donotusetheunitsifdamaged Ifproblemsoccur switchtheunitoffanddisconnectitfromthepowersupply Inordertopreventelectricshocks firesorinjuries alwaysstoptheunit disabletheprotectionswitchandcontactSAMSUNG s technicalsupportiftheunitproducessmoke ifthepowercableishotordamagedoriftheunitisverynoisy A...

Page 3: ...ions If you must install the unit in such conditions first consult your dealer Avoid installing the air conditioner In areas where it is exposed to direct sunlight Close to heat sources In damp areas or locations where it could come into contact with water for example rooms used for laundry In areas where curtains and furniture could affect the supply and discharge of air Without leaving the requi...

Page 4: ...at can support its weight Maintain sufficient clearance around the indoor unit Make sure that the water dripping from the drain hose runs away correctly and safely The indoor unit must be installed in this way that they are out of public access Not touchable by the users Insulation cover band Insulation pipe Cable tie Drain hose Installation manual Clamp If you install the cassette type indoor uni...

Page 5: ...er 80 install a 10mm thickness of polyethylene insulation or similar type of insulation on the indoor unit body Insulation installation guide Cut the part where pipes are pulled out or some curved part for insulating work When insulating a connecting duct the outlet and inlet part front back should be insulated together Insulate the end of the pipe and some curved area by using separate insulator ...

Page 6: ...4D 100FB4D 0714PX 0904DX 1004DX 090FB4P 0904PX 1254DX 100FB4P 100FB4F 1004PX 1004ZX 1254PX 1404PX 1404DX C mm 251 293 335 335 Net dimension mm 840 204 840 840 246 840 840 288 840 840 288 840 Required space for an indoor unit installation Obstruction 20mm 17mm 1500mm ormore C mm 2500mmormore ...

Page 7: ...mension mm 840 X 204 X 840 840 X 246 X 840 840 X 288 X 840 Net weight kg 15 0 16 0 18 0 20 0 Liquid pipe connection 1 4 3 8 Gas pipe connection 1 2 5 8 Drain Hose connection mm OD Φ32 0 ID Φ26 5 Drawing of the indoor unit 890 910 Celling opening 950 735 Suspension position 890 910 Celling opening 735 Suspension position Sub duct connection 55 840 370 346 185 96 950 120 45 86 164 216 55 55 840 330 ...

Page 8: ...ce the pattern sheet on the indoor unit 2 Adjust a space between the ceiling and the indoor unit by using the gauge of dimensions 3 Fix the indoor unit securely after adjusting level of the unit by using a leveler 4 Remove the pattern sheet connect the other cables and install the front panel Since the diagram is made of paper it may shrink or stretch slightly due to temperature or humidity For th...

Page 9: ...ith a pre charge of nitrogen gas insert gas Therefore all insert gas must be purged before connecting the assembly piping Unscrew the pinch pipe at the end of each refrigerant pipe Result All inert gas escapes from the indoor unit To prevent dirt or foreign objects from getting into the pipes during installation do NOT remove the pinch pipe completely until you are ready to connect the piping If t...

Page 10: ...n the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque If the pipes require brazing ensure that OFN Oxygen Free Nitrogen is flowing through the system Nitrogen blowing pressure range is 0 02 0 05MPa Oblique Rough Burr Pipe cutter Pipe Outer Diameter D Depth A ø6 35 mm 1 3 mm ø9 52 mm 1 8 mm ø12 70 mm 2 0 mm ø15 88 mm 2 2 mm ø19 05 mm 2 2 m...

Page 11: ...ixed to the wall with suitable ducts 5 Selecttheinsulationoftherefrigerantpipe Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size Less than indoor temperature of 30 C and humidity of 85 is the standard condition If installing in a high humidity condition use one grade thicker insulator by referring to the table below If installing in an unfavorable con...

Page 12: ...al clamp Large sealing pad Tighten the clamp to the maximum until you can see eight holes When installing insulation in places and conditions below use the same insulation that is used for high humidity conditions Geological condition High humidity places such as shoreline hot spring near lake or river and ridge when the part of the building is covered by earth and sand Operation purpose condition...

Page 13: ...ply force to the piping on the unit side when connecting the drain hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose to a wall frame or other support as close to the unit as possible Support pieces 1 1 5m Ceiling 1 100 or more If it is necessary to increase the height of the drainpipe install the drainpipe straightly within 300 mm from the drain hose...

Page 14: ... the drainage is performing correctly at the end of the drain pipe 5 Check for leakage at the drain pipe and drain pipe connection part 6 When leakage occurs check whether the indoor unit is level and check the drain hose connection part drainpipe connection part and drain pump connection 7 When the drainage check is completed and the condensed water remains on the drain board remove the water Tes...

Page 15: ...r Supply Max Min V Indoor Power cable 220 240V 50Hz 10 0 75 1 5mm 3wires 0 75 1 5mm 2wires Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord Code designation IEC 60245 IEC 57 CENELEC H05RN F or IEC 60245 IEC 66 CENELEC H07RN F Screws on terminal block must not be unscrewed with the torque less than 12 kgf cm Since it has the ...

Page 16: ...s refer to the installation manual CAUTION Unit mm 120 60 20 20 20 180 Power cable 3 Insert both sides of core wire of the power cable into the connection sleeve f f Method 1 Push the core wire into the sleeve from both sides Connection sleeve f f Method 2 Twist the wire cores together and push it into the sleeve Connection sleeve 4 Using a crimping tool compress the two points and flip it over an...

Page 17: ...ube contraction work is completed wrap it with the insulation tape to finish Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same level of withstand voltage with the power cable Comply with the local regulations on extensions CAUTION Insulation tape In case of extendi...

Page 18: ... SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X The procedure of setting option Settinganindoorunitaddressandinstallationoption Set the indoor unit address and installation option with remote controller option Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time You need to set twice when...

Page 19: ...e button will be selected in rotation 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SEG11 SEG12 option...

Page 20: ... enter SEG21 value Press High Fan button to enter SEG22 value Each time you press the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mode Press Low Fan button to enter SEG23 value Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation SEG16 SEG18 SEG21 SEG2...

Page 21: ...planation PAGE MODE Setting Main address RESERVED RESERVED The unit digit of an indoor unit Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 3 A single digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE RESERVED Setting RMC address RESERVED Group channel 16 Gro...

Page 22: ...ionoption suitablefortheconditionofeachinstallationlocation SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 2 RESERVED Exterior temperature sensor Central control RESERVED SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 1 Drain pump RESERVED RESERVED RESERVED Master Slave SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output S Plasma ion Buzzer Number of hours using filter SEG19 SEG20 SEG21 3 Individual...

Page 23: ... SEG14 SEG15 SEG16 SEG17 SEG18 Explanation PAGE Useofexternal control Setting the output of external control S Plasma ion Buzzer control Number of hours using filter Remote Controller Display Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 2 0 Disuse 0 Thermo on 0 Disuse 0 Useofbuzzer 2 1000Hour 1 ON OFF Contr...

Page 24: ... Details Indication Details Indication Details Indication Details Indication Details 0 D Option mode 0 F Tens digit ofSEG 0 9 Unitdigit ofSEG 0 9 The changed value 0 F When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Option SEG1 SEG2 SEG3 ...

Page 25: ...motor in the indoor unit X X X Error of the outdoor temperature sensor Error of the condensor temperature sensor Error of the discharge temperature sensor X X No communication for 2 minutes between indoor and outdoor unit communication error for more than 2minutes X X Error of outdoor unit X Detection of the float switch X X EEPROM error X EEPROM option error If you turn off the air conditioner wh...

Page 26: ...26 MEMO ...

Page 27: ...27 MEMO ENGLISH ...

Page 28: ...107 Hanamsandan 6beon ro Gwangsan gu Gwangju si Korea 62218 Samsung Electronics UK Ltd Euro QA Lab Blackbushe Business Park SaxonyWay Yateley Hampshire GU46 6GG United Kingdom AEEE Yönetmeligine Uygundur This product is RoHS compliant ...

Reviews: