32
Installation Procedure
English
Instal
lation Pr
oc
edur
e
Option
SEG13
SEG14
SEG15
SEG16
Explanation
PAGE
Use of external control
Setting the output of external
control
S-Plasma ion
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
2
0
Disuse
Sub,
Existing
Control
0
Thermo on
0
Disuse
1
On/Off
2
Off
3
Window
4
Disuse
Main,
Existing
Control
5
On/Off
6
Off
7
Window
8
Disuse
Sub,
Reverse
Control
1
Operation
on
1
Use
9
On/Off
A
Off
B
Window
C
Disuse
Main,
Reverse
Control
D
On/Off
E
Off
F
Window
Option
SEG17
SEG18
SEG19
SEG20
Explanation
Buzzer control
Number of hours using filter
PAGE
control of a remote
controller
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
0
Use of
buzzer
2
1000 Hour
3
0 or 1
Indoor 1
1
Non
use of
buzzer
6
2000 Hour
2
Indoor 2
3
Indoor 3
4
Indoor 4
Option
SEG21
SEG22
SEG23
-
Explanation
Heating setting
compensation
RESERVED
Away Set OFF Timer
-
Indication
and Details
Indication Details
Indication
Details
-
0
Disuse
0 or 1
Auto Set OFF 30Min.
-
1
2°C
2
Auto Set OFF 60Min.
2
5°C
3
Auto Set OFF 120Min.
4
Auto Set OFF 180Min.
5
Press the
button to save and complete the option setting.
6
Press the
button to exit to normal mode.
• Level control : The centralized controller can limit the functions and inputs of connected products with this function
enabled. [ Example: Operation mode limit (Cooling only/Heating only/No limitation), Heating temperature
upper limit, Cooling temperature lower limit ] To enable 'Level control' when applying the DPM with the
centralized controller, appoint the Main (Set 'Use of external control [SEG14] option to 4 or higher).
– Example : When installing DPM ( 1 Outdoor unit with 4 indoor units)