Functions
WE
Configuration
Delayed OT adaptation when OT decreases
0
CO5 -> F05 - 1
Delayed OT adaptation when OT increases
0
CO5 -> F06 - 1
3 °C/h Delay / 1 to 6 °C/h
5.6
Remote operation
Apart from measuring the room temperature, the Type 5244 Room Panel (PTC room sensor)
and Type 5257-5 Room Panel (Pt 1000 sensor) provide the following opportunities of influ-
encing the control process:
4
Selection of the operating mode: – Automatic mode
– Day mode
– Night mode
4
Set point correction: during rated operation, the room temperature set point can be in-
creased or reduced by up to 5 °C using a continuously adjustable rotary knob.
When the room sensor is activated and the remote operation (room panel) is connected and
activated, the measured room temperature is displayed. Nevertheless, it is not used for con-
trol unless the
Optimization
,
Adaptation
or
Flash adaptation
functions have been activated.
Function
WE
Configuration
Rooms sensors RF1/2
0
CO1, 2 -> F01 - 1
58
EB 5575 EN
Functions of the heating circuit
Fig. 7 · Wiring plan for Type 5244/5257-5 Room Panels to TROVIS 5575 for Rk1
or
Rk2
Type
5244/5257-5
TROVIS 5575
Rk1
Rk2
Terminal 1
Terminal 5
Terminal 3
Terminal 2
Terminal 12
Terminal 12
Terminal 3
Terminal 9
Terminal 10
Type 5244/5257-5