If a secondary heating circuit without a valve should be put out of operation, for example, in
system Anl 2.x, just its heating circuit circulation pump and not the primary circuit Rk1 is put
out of operation by using the configuration
Receive release of Rk1
.
Functions
WE
Configuration
Device bus
0
CO7 -> F01 - 1; Device bus address
Send “DHW heating active“
0
CO7 -> F20 - 1*
Receive release of Rk1
0
CO7 -> F21 - 1*
Receive release of Rk2
0
CO7 -> F22 - 1*
32
*Register no. / 5 to 64
7.11.5 Connecting a TROVIS 5570 Room Panel
A TROVIS 5570 Room Panel (accessory) can be connected to the TROVIS 5575 Controller to
measure the room temperature and for remote operation of a heating circuit. The room
panel enables direct access to the operating mode and controller time settings as well as to
all relevant parameters of a heating circuit. Additionally, the room temperature, the outdoor
temperature and, if applicable, other data points can be viewed.
The terminals 5 and 6 of the room panel are connected to terminals 14 and 15 of the con-
troller. The room panel is supplied with operating voltage (terminals 1 and 2 of the room
panel (12 to 26.5 V AC/15 to 36 V DC) at the point of installation.
Functions
WE
Configuration
Device bus
0
CO7 -> F01 - 1; Device bus address
TROVIS 5570 Room Panel in Rk1
0
CO7 -> F03 - 1; Device bus address
TROVIS 5570 Room Panel in Rk2
0
CO7 -> F04 - 1; Device bus address
7.11.6 Display error alarms issued by the device bus
Error alarms over device bus do cause controllers with an active modem function already in
the default setting to dial the control station. However, the error alarms issued by the device
bus are not displayed by controllers configured in this way. The setting CO7 -> F16 - 1
causes these controllers to react to the error alarms from the device bus by generating the
Err 5 alarm as long as the faults of the other device bus participants exist. The black squares
under the corresponding numbers at the top of the display indicate which device bus address
is defective for the first 23 device bus participants.
Function
WE
Configuration
Display error alarms issued by the device bus
0
CO7 -> F16 - 1