When the room sensor is activated and the remote room controller (room panel) is connected
and activated, the measured room temperature is displayed. Nevertheless, it is not used for
control unless the
Optimization
or
Flash adaptation
functions have been activated.
Function
WE
Configuration
Room sensor RS
0
CO1 -> F01 - 1,
option:
1
Note!
The
Day set point
adjusted via the rotary switch remains unaffected by set point corrections
performed over the room panel. Only the calculated flow temperature set point or the room
temperature set point (for flash adaptation) are adjusted accordingly.
5.6.2 Floating switch
The heating circuit can be switched to night mode by closing the switching contact if a float-
ing switch is connected to input RS.
Function
WE
Configuration
Room sensor RS
0
CO1 -> F01 - 0
5.7
Optimization
5.7.1 Advance heating depending on outdoor temperature
The controller activates rated operation of the heating system before the time-of-use starts de-
pending on the outdoor temperature. The
Advance heating time
refers to an outdoor temper-
ature of –12 °C. In case of higher outdoor temperatures, the advance heating time is
reduced.
This means, the colder it is outside, the earlier the night set-back is terminated to ensure that
the desired room temperature
Day set point
has been reached at the beginning of the
time-of-use, if possible.
Functions
WE
Configuration
Optimization
0
120 min
CO1 -> F02 - 1,
option
: 1
Advance heating time / 0 to 360 min
Outdoor temperature t
A
1
CO1 -> F07 - 1
EB 5433 EN
45
Functions of the heating circuit