1.6.2 Setting vacation periods
During vacation periods, the heating constantly remains in reduced operating mode. The
DHW heating is monitored for frost protection, if necessary. A maximum of 10 vacation pe-
riods can be entered.
Parameter
WE
Level / Range of values
Vacation period (START, STOP)
–
PA-SYS / 01.01 to 31.12 (1 Jan to 31 Dec)
Adopt public holidays and
vacations for DHW
0
CO2 -> F07 - 1
Proceed as follows:
Turn rotary switch “Configuration and
parameterization“ to
COPA
.
Display shows:
0
,
NR
blinks.
q
Set valid key number.
Confirm key number.
Display shows:
PA 1
q
Select parameter level PA-SYS.
Open parameter level PA-SYS.
q
Select “Vacation periods“.
Display shows:
Open “Vacation periods“
Display shows:
START
q
If applicable, select
– –.– –
.
Activate editing mode for start date of vacation period.
START
and
blink.
q
Edit start date of vacation period.
Confirm start date of vacation period.
Display shows:
STOP
, start date of vacation period
q
Edit end of vacation period.
Confirm end of vacation period.
To enter additional vacation periods, re-select
– –.– –
and repeat the steps in the fields
highlighted in gray.
EB 5433 EN
15