1.6
Setting the times-of-use
Three times-of-use can be set for each day of the week.
If a time-of-use is not required, its start and stop times must be set to identical times.
The times-of-use for heating and the DHW circulation pump are set using the top rotary
switch:
Times-of-use
Position
Heating
DHW circulation pump
Parameters
WE*
Rotary switch / Range of values
Period/day
1
1, 2, 3, 4, 5, 6, 7 with 1-7 = every day,
1 = Monday, 2 = Tuesday, ..., 7 = Sunday
Start first time-of-use
7:00
0:00 h to 24:00 h; in steps of 30 minutes
Stop first time-of-use
22:00
0:00 h to 24:00 h; in steps of 30 minutes
Start second time-of-use
22:00
0:00 h to 24:00 h; in steps of 30 minutes
Stop second time-of-use
22:00
0:00 h to 24:00 h; in steps of 30 minutes
Start third time-of-use
22:00
0:00 h to 24:00 h; in steps of 30 minutes
Stop third time-of-use
22:00
0:00 h to 24:00 h; in steps of 30 minutes
*Default setting (WE) valid for heating (switch position
)
Note!
The times-of-use for DHW heating are set in parameter level PA2 similar to the times-of-use
for heating and the DHW circulation pump.
EB 5433 EN
11
Operation