74
EB 8384-5 EN
Start-up and settings
Perform zero calibration:
Init mode
Default
MAX
Turn
Code 6
Press
, Code
6
blinks.
Turn
ZP
Î
Press INIT key.
Zero calibration starts. The positioner
moves the valve to the CLOSED position
and recalibrates the internal electrical
zero point.
7.8
Reset to default settings
This function resets all start-up parameters as
well as the diagnosis to the factory default
settings (see code list in section 14).
Enable configuration:
Turn
g
Code 3, display:
No
Press
, Code
3
blinks.
Turn
YES
Press
, display:
Reset start-up parameters:
Reset
Default:
No
Turn
g
Code 36, display: ••–••–
Press
, Code
36
blinks.
Turn
Std
Press .
All start-up parameters as well as the diag-
nosis are reset to their default values.
Note:
Code 36 - diAG allows just the diag
-
nosis data (EXPERTplus) to be reset.
Refer to the Operating Instructions for
EXPERTplus valve diagnostics
u
EB 8389.
Summary of Contents for FOUNDATION 3730-5
Page 106: ...106 EB 8384 5 EN...
Page 107: ...EB 8384 5 EN 107...
Page 108: ...108 EB 8384 5 EN...
Page 109: ...EB 8384 5 EN 109...
Page 110: ...110 EB 8384 5 EN...
Page 111: ...EB 8384 5 EN 111...
Page 112: ...112 EB 8384 5 EN...
Page 113: ...EB 8384 5 EN 113...
Page 114: ...114 EB 8384 5 EN...
Page 115: ...EB 8384 5 EN 115...
Page 116: ...116 EB 8384 5 EN...
Page 117: ...EB 8384 5 EN 117...
Page 118: ...118 EB 8384 5 EN...
Page 119: ...EB 8384 5 EN 119...
Page 120: ...120 EB 8384 5 EN...
Page 121: ...EB 8384 5 EN 121...
Page 122: ...122 EB 8384 5 EN...
Page 123: ...EB 8384 5 EN 123...
Page 124: ...124 EB 8384 5 EN...
Page 125: ...EB 8384 5 EN 125...
Page 126: ...126 EB 8384 5 EN...
Page 127: ...EB 8384 5 EN 127...
Page 128: ...128 EB 8384 5 EN...
Page 129: ...EB 8384 5 EN 129...
Page 130: ...130 EB 8384 5 EN...
Page 131: ...EB 8384 5 EN 131...