8-2
EB 8075 EN
Malfunctions
Malfunction
Possible reasons
Recommended action
Increased flow through
closed valve (seat leak-
age)
Dirt or other foreign
particles deposited
between the seat and
piston
Shut off the section of the pipeline and flush the
valve.
Valve trim is worn out.
Contact our after-sales service.
Gasket underneath the
seat bridge is worn out.
Contact our after-sales service.
Gasket at the cage is
worn out.
Contact our after-sales service.
The valve leaks to the
atmosphere (fugitive
emissions).
Defective packing
Contact our after-sales service.
Version with adjustable
packing
1)
: packing not
tightened correctly
Adjust the packing (see information under
'Adjusting the packing' in the 'Testing the installed
valve' section). Contact our after-sales service
when it continues to leak.
Version with bellows
seal: the bellows seal is
defective.
Contact our after-sales service.
Flange joint loose or
gasket worn out
Check the flange joint.
Contact our after-sales service.
1)
See the 'Markings on the device' section
Contact our after-sales service for malfunctions not listed in the table.