EB 3964 EN 

 13

Electrical connection

4.1 

Connecting cable

A connector type C according to 

EN 175301-803 (distance between contacts 
8 mm) or a connector type C according to 

industrial standard (distance between con-

tacts 9.4 mm) is used for the electrical con

-

nection.
Observe 

clause 12 of EN 60079-14: 2008

 

(VDE 0165, Part 1) for installation of the 
intrinsically safe circuits. Clause 12.2.2.7 

applies when running multi-core cables and 
wires with more than one intrinsically safe 
circuit.
Preferably use connecting lines with mini-

mum 0.5 mm² conductor cross-section and 
3.5 to 6 mm outside diameter.

The radial thickness of the insulation of a 
conductor for common insulating materials 
(e.g. polyethylene) must not be smaller than 

0.2 mm. The diameter of an individual wire 
in a fine-stranded conductor must not be 
smaller than 0.1 mm. Protect the conductor 

ends against splicing, e.g. by using wire-end 
ferrules.

1

2

Fig. 6: 

Wiring diagram for connector

Adhere to the terminal assignment. Switch

-

ing the assignment of the electrical terminals 

may cause the explosion protection to be

-

come ineffective.

Do not loosen enameled screws in or on the 

housing.

The maximum permissible values specified in 
the EC type examination certificates apply 
when interconnecting intrinsically safe elec

-

trical equipment (U

i

 or U

0

, l

i

 or I

0

, P

i

 or P

0

, C

i

 

or C

0

 and L

i

 or L

0

). See page 15.

4.2 

Devices for Zones 2 and 

22

In equipment operated according to type of 

protection Ex nA II (non-sparking equipment) 
according to EN 60079-15:2003, circuits 

may be connected, interrupted or switched 
while energized only during installation, 
maintenance or repair.
Equipment connected to energy-limited cir-

cuits with type of protection Ex nL (ener

-

gy-limited equipment) according to 

EN 60079-15:2003 may be switched under 

normal operating conditions.

The maximum permissible values specified in 

the statement of conformity or its addenda 

(see page 

13) apply when interconnecting 

the equipment with energy-limited circuits in 

type of protection Ex nL IIC.

WARNING

!

Summary of Contents for 3964

Page 1: ...Translation of original instructions EB 3964 EN Type 3964 Solenoid Pilot Valve with and without CNOMO adapter plate Type 3964 Solenoid Pilot Valve Edition December 2011...

Page 2: ...fter sales Service Department aftersalesservice samson de The mounting and operating instructions for the devices are included in the scope of delivery The latest documentation is available on our web...

Page 3: ...h CNOMO adapter plate without booster 9 2 3 Devices with CNOMO adapter plate and booster 10 3 Pneumatic connection 10 3 1 Pilot supply 10 3 2 Devices with interface for direct mounting 11 3 3 Devices...

Page 4: ...aining their knowledge and experience as well as their knowledge of the applicable standards Explosion protected versions of this device must be operated only by personnel who has undergone special tr...

Page 5: ...ate 30 mm 1 KVS coefficient 0 01 without booster 0 0 02 including booster 1 Pressure reducer Without pressure reducer 0 Electrical connection Device connector according to EN 175301 803 without cable...

Page 6: ...ic data Pilot supply Medium Instrument air free from corrosive substances Pressure 1 4 to 2 0 bar 3 0 to 3 6 bar 3 0 to 8 0 bar Output signal Without booster 1 2 bar at 1 4 bar pilot supply 1 8 bar at...

Page 7: ...bient temperature in temperature class T6 20 to 60 C T5 20 to 70 C T4 20 to 80 C Type of protection Ex nA II 3 for use in hazardous areas Zone 2 Type 3964 81 82 83 Ambient temperature in temperature c...

Page 8: ...ve the enclo sure and at least 200 mm clearance at the electrical connection Exhaust air filter Fig 1 Type 3964 Installation WARNING 2 1 Devices with interface for direct mounting Type 3964 XXX000X000...

Page 9: ...il 1400 5931 1 piece 2 pieces 1 Cap screw ISO 1207 M3 8 If required Fig 2 Type 3964 Accessories 2 2 Devices with CNOMO adapter plate without booster Type 3964 XXX100X00XXX Devices with CNOMO adapter p...

Page 10: ...r 3 Pneumatic connection Run and attach the connecting lines and screw joints according to good professional practice Check them for leakage and dam age at regular intervals and repair them if necessa...

Page 11: ...rt switching times can be achieved by keeping the hose length as short as possible To prevent dirt particles entering a filter with 30 m mesh size is installed in the pilot supply port When the filter...

Page 12: ...m pressure 3 See technical data provided by the valve manufacturer for the valve size 4 Electrical connection For electrical installation observe the rele vant electrotechnical regulations and the ac...

Page 13: ...2 Fig 6 Wiring diagram for connector Adhere to the terminal assignment Switch ing the assignment of the electrical terminals may cause the explosion protection to be come ineffective Do not loosen ena...

Page 14: ...l signal is not available see Fig 7 Use solenoid pilot valves without manual override for safety circuits 4 5 Certificates The certificates valid at the time when these instructions were published are...

Page 15: ...EB 3964 EN 15...

Page 16: ...16 EB 3964 EN...

Page 17: ...EB 3964 EN 17...

Page 18: ...18 EB 3964 EN...

Page 19: ...EB 3964 EN 19...

Page 20: ...20 EB 3964 EN...

Page 21: ...EB 3964 EN 21...

Page 22: ...22 EB 3964 EN...

Page 23: ...EB 3964 EN 23...

Page 24: ...24 EB 3964 EN...

Page 25: ...EB 3964 EN 25...

Page 26: ...26 EB 3964 EN 28V 115mA no limited 0nF 0 H 28V 115 mA 250mW 0nF 0 H 28V 240 115mA 28V 0mA 28V 785 115mA 28V 0mA T6 T5 T4 60 C 45 C ta 70 C 80 C...

Page 27: ...EB 3964 EN 27 Model 3964 3 Pilot Valve solenoid valve circuit Model 3964 3 Pilot Valve signal circuit UNSPECIFIED APPARATUS e g transistor relay transmitter...

Page 28: ...f conformity is issued under the sole responsibility of the manufacturer Die alleinige Verantwortung f r die Ausstellung dieser Konformit tserkl rung tr gt der Hersteller Nous certifions pour les prod...

Page 29: ...t mit den einschl gigen Harmonisierungsrechtsvorschriften der Union best tigt the conformity with the relevant Union harmonisation legislation is declared with est conforme la l gislation d harmonisa...

Page 30: ...e Bundesanstalt Bundesallee 100 D 38116 Braunschweig Benannte Stelle Notified Body Organisme notifi 0102 wird die Konformit t mit den einschl gigen Harmonisierungsrechtsvorschriften der Union best tig...

Page 31: ...sche Bundesanstalt Bundesallee 100 D 38116 Braunschweig Benannte Stelle Notified Body Organisme notifi 0102 wird die Konformit t mit den einschl gigen Harmonisierungsrechtsvorschriften der Union best...

Page 32: ...2019 04 04 English SAMSON AKTIENGESELLSCHAFT Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de www samson de EB 3964 EN...

Reviews: