22
EB 8395 EN
Operating the positioner
Volume restriction Q
The volume restriction serves to adapt the air
output capacity to the size of the actuator.
Two fixed settings are possible (refer to sec
-
Reading
Display
Meaning
ESC
Stop
Err
Faults
LOW
w too low
MAN
Manual mode
MAX
Maximum range
RST
Reset
INIT
Initialization
ON/OFF
Activated/deactivated
ZERO
Zero calibration
Icons which are assigned to certain codes
and functions are indicated on the display.
The bar elements indicate the system devia-
tion that depends on the sign (+/–) and the
value.
One bar element appears per 1 % set point
deviation.
If the positioner has not yet been initialized,
the position of the pick-up rod is indicated in
the operating range of ±10 mm.
If the fault indication icon is displayed,
press or until
ERR
is displayed to view
the relevant
E0
to
E15
error code(s) (see
code list in section 33 on page 9.1).
7 Operating the positioner
The process is disturbed by the movement of
the actuator stem.
Do not perform the initialization while the
process is running. First isolate the plant by
closing the shut-off valves.
Î
Perform pneumatic connections on the
actuator as described in
u
Î
Connect the supply air to signal pressure
connection.
Î
Check whether a vent plug or silencer is
screwed into the exhaust port.
Î
Connect the 4 to 20 mA signal.
à
Ter11/–12
Î
Connect software limit contacts, if appli
-
cable.
à
Ter41/–42:
(limit contact 1, min.)
à
Ter51/–52:
(limit contact 2, max.)
−
LOW
on the display indicates that the
reference variable is lower than 3.8 mA.
−
The positioner is ready for operation with
its default settings for most applications.
NOTICE
!
Note
Summary of Contents for 3724