Operating the positioner
If no settings are entered within three min-
utes, the enabled configuration function be
-
comes invalid.
7.3 Adjusting the volume re-
striction Q
The volume restriction Q serves to adapt the
air output capacity to the size of the actua
-
tor:
−
Actuators with a
transit time < 0.4 s
re-
quire a restricted air flow rate.
Setting to MIN
−
Actuators with a
transit time ≥ 0.4 s
do
not require the air flow rate to be restrict
-
ed.
Setting to MAX
Intermediate settings are not permitted.
Malfunction due to changing the volume re
-
striction setting!
Re-initialize positioner after changing the
volume restriction setting.
NOTICE
!
MIN position:
Arrow points toward the positioner
MAX position:
Arrow points away from the
positioner
Position of the volume restriction Q
Fig. 7:
Setting of the volume restriction