30
EB 8395 EN
Operating the positioner
Positioner that has not been initialized
Press
or for a long time to move the
valve manually.
The valve is only moved in one direction un-
controlled. The bar elements on the display
indicate the change in direction.
Press
to deactivate manual mode.
The Manual mode function can only be exit
-
ed as described or by interrupting the elec
-
trical supply (cold start). The positioner does
not
automatically exit this function and re
-
turn to the display showing the status indica-
tion.
7.12 Reset
A reset causes an initialization to be undone
and all parameters settings are reset to the
default settings (see code list in sec
-
tion 11.2).
Enable configuration (section 7.2).
Press
or
until Code
P18
appears.
Press
and hold for six seconds.
6-5-4-3-
2-1-
is counted down on the display.
RST
blinks while is pressed. As soon as
the key is released, the reset process is com-
pleted and the display returns to status indi-
cation (
P0)
.
The fault indication icon is displayed after
a reset since the positioner needs to be
re-initialized. The error code
E2
is also acti-
vated (see section 9.1).
Note
Note