SAMLEX AMERICA INC. | 35
6.2 protectionS anD monitorinG in cHarGer / GriD paSS
tHouGH moDe
note: please refer to table 6.2 for status of monitoring LeDs for various protections /
operational conditions explained below:
In this mode, Grid AC Power is available, is being passed through to the Load(s) and Bat
-
tery Charger is charging the batteries:
6.2.1 overload / Short circuit protection in ac Load(s)
15A Breaker (4, Fig 3.1) in the AC Input Circuit of the unit provides protection against
overload and short circuit in the AC loads when the unit is in Grid AC Power Pass
Through Mode.
6.2.2 overload / Short circuit protection in ac input circuit of
Battery charger
5A, 250V fuse (5, Fig 3.1) is provided in the AC input circuit of the Battery Charger to
protect the battery Charger against overload and short circuit.
6.2.3 protection against Ground fault in ac Loads
AC input to the unit is required to be fed from 15A GfCI protected AC outlet of Grid AC
Power. In case of Ground fault in the AC load(s), the GFCI in the 15A GFCI protected AC
outlet of Grid AC Power will trip.
table 6.2 protections & monitoring: Battery charger / Grid ac power pass through mode
LeD Display
other Symptoms
possible cause(s)
remedy
Green LeD
“CHArGer”
(7, Fig 3.1) is ON
• Charging is normal
• AC output voltage is
not available
Unit is in Grid Pass
Through Mode but the
15A AC Input breaker on
the unit (4, Fig 3.1) has
tripped due to continu-
ous overload of > 15A
or due to short circuit on
the AC load side
• Ensure that the
maximum continu
-
ous load is < 15A
• Check and remove
short circuit on the
AC load side
• Reset the 15A
breaker on the unit
Green LeD
“CHArGer”
(7, Fig 3.1) is OFF
• Charging has stopped
• Grid voltage is avail
-
able at the power cord
• AC output is available
• Charging has stopped
as Grid input voltage
is > 143VAC
• Unit is still in Grid
Pass Through Mode
Charging will resume
automatically when
Grid AC input voltage
drops to < 138VAC
• Charging has stopped
as Grid input voltage
is < 10VAC
• Unit is still in Grid
Pass Through Mode
Charging will resume
automatically when
Grid AC input voltage
rises to > 75VAC
SeCTIOn 6 |
Protections, Monitoring
& Troubleshooting