Troubleshooting & Maintenance

TROUBLESHOOTING

Table 4.1 given below provides troubleshooting guidance

Table 4.1: TROUBLESHOOTING GUIDE

Symptom

Possible 

Reason

Remedy

Charging Status LED Indicator (1) is 

OFF during daytime when PV panels 

are exposed to direct sunlight 

Input connec-

tion from solar 

panels has been 

disconnected or PV 

Voltage is <5V

Check that wiring from solar panels to 

the Solar Panel Input Connections is con-

nected and connections are tight. Check 

PV Voltage is >6V.

Battery Status LED Indicator (2) is 

Green and is flashing fast

Battery voltage has 

risen to the Over 

Voltage Disconnect 

Threshold of 16.0V

Measure battery voltage. If ≥ than 16.0V, 

disconnect the battery. The controller is 

defective. Call Technical Support.

Battery Status LED Indicator (2) is 

steady Orange. Battery voltage at 

Load Terminals is available and the 

load is operating normally

Battery voltage has 

dropped to Under 

Voltage Warning 

Threshold of 12.0V

The Battery Status Indicator (1) will return 

to Green when the battery voltage rises 

to Under Voltage Warning Reconnect 

Threshold of 12.2V.

Battery Status LED Indicator (2) is 

steady Red. There is no battery volt-

age at Load Terminals and the load 

has switched off

Battery voltage has 

dropped to Low 

Battery Disconnect 

Threshold of 11.1V

The Battery Status Indicator (1) will reset 

to Green when the battery voltage rises 

to Low Battery Reconnect Threshold 

of 12.6V. Battery voltage will then be 

restored at the Load Terminals. 

Load Status LED Indicator (3) is Red 

and flashing slowly. There is no 

output voltage at Load Terminals and 

the load has switched off

Current drawn 

from the Load Ter-

minals is > 10A

Reduce the load to < 10A. Press the Load 

On/Off Button (4). After 3 sec, the output 

voltage at the Load Terminals will be 

restored. 

Load Status LED Indicator (3) is Red 

and flashing fast. There is no output 

voltage at Load Terminals and the 

load has switched off

There is short 

circuit at the Load 

Terminals

Clear the short Circuit. Press the Load On/

Off Button (4). After 3 sec, the output 

voltage at the Load Terminals will be 

restored and the load will once again start 

operating normally. 

All 3 LED Indicators are flashing:

Charging Status LED (1) = Flashes Green
Battery Status LED (2) = Flashes Orange
Load Status LED (3) = Flashes Red

Heat sink is over-

heated.

When the heat sink temperature is >85°C, 

the input and output circuits will be cut 

off. Once the temperature falls below 

75°C, operation will be resumed. 

All 3 LED Indicators are flashing:

Charging Status LED (1) = Flashes Green
Battery Status LED (2) = Flashes Red
Load Status LED (3) = Flashes Red

System error. 

Battery voltage 

does not match 

controller

Check battery voltage and ensure it is 

12V. Press Load On/Off Button (4) to clear 

the malfunction.

MAINTENANCE

Dust and dirt should be swept off the solar panel surface using soft brush. Then, a wet cloth 

may be used to wipe the panel surface to remove remaining dirt and grime. It is recommended 

that any bird droppings should be removed as soon as possible as these can cause damage to 

the surface.

Summary of Contents for MSK-135

Page 1: ...Portable Solar Charging Kit MSK 90 MSK 135 Please read this manual BEFORE using your Portable Solar Charging Kit Owner s Manual ...

Page 2: ...NUAL Index SECTION 1 Safety Instructions 3 SECTION 2 Description Applications Features 5 SECTION 3 Layout 7 SECTION 4 Installation Operation 9 SECTION 5 Troubleshooting Maintenance 12 SECTION 6 Specifications 13 SECTION 7 Warranty 15 ...

Page 3: ...Positive terminal of the solar array input on the Charge Con troller or the Positive terminal of the battery DO NOT ground the Negative 3 To reduce the risk of injury charge only 12V Lead Acid Batteries Sealed AGM types Other types of batteries may be subject to bursting which can lead to per sonal injury and damage 4 Comply with battery manufacturer s recommendations 5 Avoid charging damaged defe...

Page 4: ...a dark cover over the panels when handling panels that have bare un insulated output wires Accidental shorting of panel terminals or wiring connected to the panels can result in spark causing personal injury or a fire hazard 15 It is important that the battery gets fully charged frequently at least once per week Otherwise the battery can become permanently damaged due to under charging Partially c...

Page 5: ...anels Panels are built with strong anodized aluminum frames and high transpar ency solar glass for maximum light permeability and high efficiency Maximizing Solar Energy Capture and System Efficiency with Tilting Arrange ment Folding type of support legs with tilt adjustment arrangement have been provided The unfolded solar array can be conveniently pointed towards the direction azimuth of the sun...

Page 6: ...e 4 Stages of charging for 100 return of capacity and long battery life Bulk Ab sorption Boost Equalization and Float Stages User friendly LED display for monitoring of operation and self diagnostics for troubleshooting Integrated Temperature Sensor for temperature compensation to ensure improved charging of batteries that experience wider temperature variations during the year MOSFET based revers...

Page 7: ...e 50A Mating Type Battery Connector Battery Clamps 9B Red Positive Battery Clamp 9C Black Negative Battery Clamp 10 2 ft Adapter Cable with 2 Pole 50A Mating Type Battery Connector SAE Connector 10B SAE Connector 11 10A Fuse and Fuse Holder 12 12V Battery not included 13 Fuse for load s connected directly to the battery not included 14 12V load connected directly to the battery 15 Carrying Case Fi...

Page 8: ...em voltage error Charging Load and Battery Status LED Orange flashing simultaneously Controller overheating SECTION 3 Layout CHARGING STATUS 1 BATTERY STATUS 2 Charging Status LED Indicator 1 Battery Status LED Indicator 2 Load Status LED Indicator 3 Load ON OFF Button 4 LOAD STATUS 3 PV Positive PV Negative Load Positive Load Negative Battery Positive Battery Negative NOTE RJ 45 RS 485 Communicat...

Page 9: ... to the PV and PV terminals of the Charge Controller Fig 3 2 through their respective Junction Boxes 6 Fig 3 1 No ad ditional connection is required to be made Connection of Battery or Battery Bank to the Charge Controller The following arrangement has been provided for connecting the Charge Controller to the battery Battery Terminals of the Charge Controller Fig 3 2 are prewired to 14ft cable wit...

Page 10: ...f the load when the battery drops below 11 1V The load will be automati cally re connected after the battery has recharged to 12 6V The load is protected against overload 10A Connection of Loads 10A Directly to the Battery Loads 10A 14 Fig 3 1 should be connected directly to the battery through appropri ate fuse and cable rated at 1 25 times the continuous DC input current of the load Fig 3 1 The ...

Page 11: ...e polarity no damage to the controller will result Correct the polarity to resume normal operation Battery Voltage Error If battery voltage does not match controller operating voltage controller will stop working After correcting the voltage the failure can be eliminated by pushing the Load ON OFF Button 4 Damaged Temperature Sensor If the temperature sensor is short circuited or damaged the contr...

Page 12: ...of 12 6V Battery voltage will then be restored at the Load Terminals Load Status LED Indicator 3 is Red and flashing slowly There is no output voltage at Load Terminals and the load has switched off Current drawn from the Load Ter minals is 10A Reduce the load to 10A Press the Load On Off Button 4 After 3 sec the output voltage at the Load Terminals will be restored Load Status LED Indicator 3 is ...

Page 13: ... 85 C 40 F to 185 F INGRESS PROTECTION IP RATING IP 65 Waterproof STANDARD TEST CONDITIONS STC FOR SOLAR MODULE Irradiance Level 1000W m2 Spectrum AM1 5 Cell Temperature 25 C 77 F OTHER COMPONENTS PARAMETERS CABLE SETS FOR BATTERY Main Cable Set 14ft cable pre wired to Charge Controller Battery end has 2 Pole 50A Mating Type Battery Connector and 10A fuse Adapter Set 1 2 Pole 50A Mating Type Batte...

Page 14: ... Cycle Battery Voltage drops to 10 8V Float Voltage Vf 13 8V Exit to Absorption Boost when in Float Stage 13 2V Under Voltage Warning 12 0V LED Battery Status Indicator Orange Under Voltage Warning Auto Reset 12 2V Over Voltage Limit 15 5V Charging Stops Over Voltage Limit Auto Reset 15 0V Charging Resumes Over Voltage Disconnect Indication 16 0V Control on Load Terminals Low Battery Disconnect 11...

Page 15: ...s unable to remedy the defect after having a reasonable number of opportunities to do so Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misuse of the equipment including exposure to excessi...

Page 16: ...0 561 5885 Fax 888 814 5210 Local Numbers Ph 604 525 3836 Fax 604 525 5221 Website www samlexamerica com USA Shipping Warehouse Kent WA Canadian Shipping Warehouse Delta BC Email purchase orders to orders samlexamerica com 11023 MSK 90 135 0415 ...

Reviews: