background image

10  |  SAMLEX AMERICA INC.    

 

Connect the Battery as follows:
1.  Connect the Battery Alligator Clips to the Battery Terminals. 

IMPORTANT: OBSERVE 

POLARITY.

 Be careful to attach the RED Positive Battery Clamp (9B, Fig 3.1) to ‘Posi-

tive’ or ‘+’ of the battery and the black Negative Battery Clamp (9C, Fig 3.1) to the 
‘Negative’ or ‘-’ of the battery. If polarity is reversed accidentally, no permanent 
damage will occur, but the 10A in-line fuse (11, Fig 3.1) will blow. In this case, cor-
rect the polarity and replace the fuses.

2.  If SAE type of battery inlet is provided on the vehicle, use the 2-Pole, 50A Mating 

Type Battery Connector to SAE Adapter Cable (10, Fig 3.1).

3.  Removal of the battery from the vehicle is not necessary provided the battery is 

being charged in a well-ventilated area. 

4.  It is recommended that the kit be attached to the battery at the beginning of each 

camping event rather than wait until the battery is dead before connecting. This 
allows the solar charging system to supply the loads on the battery and fully charge 
it each day. 

Connection of Loads <10A to the Load Terminals of the Charge Controller

The Charge Controller is provided with Load Terminals (Fig 3.2) for powering small loads 
of up to 10A (max 100 W). Load powered from these terminals provide the following 
benefits:
• 

The battery will be protected against deep discharge as the Charge Controller will 
cut off the load when the battery drops below 11.1V. The load will be automati-
cally re-connected after the battery has recharged to 12.6V.

• 

The load is protected against overload (≥ 10A)

Connection of Loads >10A Directly to the Battery

Loads >10A (14, Fig 3.1) should be connected directly to the battery through appropri-
ate fuse and cable rated at 1.25 times the continuous DC input current of the load (Fig 
3.1). The fuse (13, Fig 3.2) should be located as close to the battery as possible (within 7" 
of Battery Positive). The fuse is required to protect the cable run from the battery to the 
load against overheating/fire due to short circuit along the cable run. The cable should 
be sized based on amacity = 1.25 times the continuous current or 2% voltage drop, 
whichever is thicker.

 

!

  CAUTION!

Please note that the Solar Modules are permanently connected to the Input Terminals 
of the Charge Controller. The modules will start generating power as soon as these are 
exposed to sunlight. However, there will be no power output from the Charge Control-
ler until the controller is connected to the battery. Make sure that the battery voltage is 
> 6V in order to start the Charge Controller. The following spurious LED indications may 
be seen at the Charge Controller and may be disregarded:

• 

Solar panels are exposed to sunlight and battery has not been connected:

- No LED indication

• 

Solar Panels are exposed to sunlight, battery is connected and then removed: 

- Charging Status LED (1, Fig 3.2) .........Steady GREEN
- Battery Status LED (2, Fig 3.2).............Steady GREEN with RED flickering

SECTION 4  |  

Installation & Operation

Summary of Contents for MSK-135

Page 1: ...Portable Solar Charging Kit MSK 90 MSK 135 Please read this manual BEFORE using your Portable Solar Charging Kit Owner s Manual ...

Page 2: ...NUAL Index SECTION 1 Safety Instructions 3 SECTION 2 Description Applications Features 5 SECTION 3 Layout 7 SECTION 4 Installation Operation 9 SECTION 5 Troubleshooting Maintenance 12 SECTION 6 Specifications 13 SECTION 7 Warranty 15 ...

Page 3: ...Positive terminal of the solar array input on the Charge Con troller or the Positive terminal of the battery DO NOT ground the Negative 3 To reduce the risk of injury charge only 12V Lead Acid Batteries Sealed AGM types Other types of batteries may be subject to bursting which can lead to per sonal injury and damage 4 Comply with battery manufacturer s recommendations 5 Avoid charging damaged defe...

Page 4: ...a dark cover over the panels when handling panels that have bare un insulated output wires Accidental shorting of panel terminals or wiring connected to the panels can result in spark causing personal injury or a fire hazard 15 It is important that the battery gets fully charged frequently at least once per week Otherwise the battery can become permanently damaged due to under charging Partially c...

Page 5: ...anels Panels are built with strong anodized aluminum frames and high transpar ency solar glass for maximum light permeability and high efficiency Maximizing Solar Energy Capture and System Efficiency with Tilting Arrange ment Folding type of support legs with tilt adjustment arrangement have been provided The unfolded solar array can be conveniently pointed towards the direction azimuth of the sun...

Page 6: ...e 4 Stages of charging for 100 return of capacity and long battery life Bulk Ab sorption Boost Equalization and Float Stages User friendly LED display for monitoring of operation and self diagnostics for troubleshooting Integrated Temperature Sensor for temperature compensation to ensure improved charging of batteries that experience wider temperature variations during the year MOSFET based revers...

Page 7: ...e 50A Mating Type Battery Connector Battery Clamps 9B Red Positive Battery Clamp 9C Black Negative Battery Clamp 10 2 ft Adapter Cable with 2 Pole 50A Mating Type Battery Connector SAE Connector 10B SAE Connector 11 10A Fuse and Fuse Holder 12 12V Battery not included 13 Fuse for load s connected directly to the battery not included 14 12V load connected directly to the battery 15 Carrying Case Fi...

Page 8: ...em voltage error Charging Load and Battery Status LED Orange flashing simultaneously Controller overheating SECTION 3 Layout CHARGING STATUS 1 BATTERY STATUS 2 Charging Status LED Indicator 1 Battery Status LED Indicator 2 Load Status LED Indicator 3 Load ON OFF Button 4 LOAD STATUS 3 PV Positive PV Negative Load Positive Load Negative Battery Positive Battery Negative NOTE RJ 45 RS 485 Communicat...

Page 9: ... to the PV and PV terminals of the Charge Controller Fig 3 2 through their respective Junction Boxes 6 Fig 3 1 No ad ditional connection is required to be made Connection of Battery or Battery Bank to the Charge Controller The following arrangement has been provided for connecting the Charge Controller to the battery Battery Terminals of the Charge Controller Fig 3 2 are prewired to 14ft cable wit...

Page 10: ...f the load when the battery drops below 11 1V The load will be automati cally re connected after the battery has recharged to 12 6V The load is protected against overload 10A Connection of Loads 10A Directly to the Battery Loads 10A 14 Fig 3 1 should be connected directly to the battery through appropri ate fuse and cable rated at 1 25 times the continuous DC input current of the load Fig 3 1 The ...

Page 11: ...e polarity no damage to the controller will result Correct the polarity to resume normal operation Battery Voltage Error If battery voltage does not match controller operating voltage controller will stop working After correcting the voltage the failure can be eliminated by pushing the Load ON OFF Button 4 Damaged Temperature Sensor If the temperature sensor is short circuited or damaged the contr...

Page 12: ...of 12 6V Battery voltage will then be restored at the Load Terminals Load Status LED Indicator 3 is Red and flashing slowly There is no output voltage at Load Terminals and the load has switched off Current drawn from the Load Ter minals is 10A Reduce the load to 10A Press the Load On Off Button 4 After 3 sec the output voltage at the Load Terminals will be restored Load Status LED Indicator 3 is ...

Page 13: ... 85 C 40 F to 185 F INGRESS PROTECTION IP RATING IP 65 Waterproof STANDARD TEST CONDITIONS STC FOR SOLAR MODULE Irradiance Level 1000W m2 Spectrum AM1 5 Cell Temperature 25 C 77 F OTHER COMPONENTS PARAMETERS CABLE SETS FOR BATTERY Main Cable Set 14ft cable pre wired to Charge Controller Battery end has 2 Pole 50A Mating Type Battery Connector and 10A fuse Adapter Set 1 2 Pole 50A Mating Type Batte...

Page 14: ... Cycle Battery Voltage drops to 10 8V Float Voltage Vf 13 8V Exit to Absorption Boost when in Float Stage 13 2V Under Voltage Warning 12 0V LED Battery Status Indicator Orange Under Voltage Warning Auto Reset 12 2V Over Voltage Limit 15 5V Charging Stops Over Voltage Limit Auto Reset 15 0V Charging Resumes Over Voltage Disconnect Indication 16 0V Control on Load Terminals Low Battery Disconnect 11...

Page 15: ...s unable to remedy the defect after having a reasonable number of opportunities to do so Warranty service shall be performed only by the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misuse of the equipment including exposure to excessi...

Page 16: ...0 561 5885 Fax 888 814 5210 Local Numbers Ph 604 525 3836 Fax 604 525 5221 Website www samlexamerica com USA Shipping Warehouse Kent WA Canadian Shipping Warehouse Delta BC Email purchase orders to orders samlexamerica com 11023 MSK 90 135 0415 ...

Reviews: